No comment |
>
Control System >
PLC >
Mitsubishi PLC >
FX3U-16MT-ESS PLC 100?40V AC 8DI 8DO Transistor Mitsubishi with Programing CableFX3U-16MT-ESS Mitsubishi PLC Base Unit Original Brand NEW
General Specifications [Main Unit]
Item
Ambient
temperature
Ambient temperature
0 to 55°C (32 to 131°F) when operating and -25 to 75°C (-13 to 167°F) when stored
Ambient humidity
5 to 95%RH (no condensation) when operating
Vibration resistance
Conforms to EN 68-2-6
Frequency
(Hz)
Acceleration
(m/s
2
)
Half
amplitude
(mm)
Sweep Count
for X, Y, Z: 10
times
(80 min in
each direction)
When
installed
on DIN
rail
10 to 57
--
0.035
57 to 150
4.9
--
When
installed
directly
10 to 57
--
0.075
57 to 150
9.8
--
Shock resistance
Compliant with EN 68-2-27
(147 m/s2Acceleration, Action time: 11ms, 3 times by
half-sine pulse in each direction X, Y, and Z)
Noise resistance
By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 µs, rise time of 1 ns and period of 30
to 100 Hz
Dielectric withstand voltage*1
1.5kV AC for one minute
Compliant with JEM-1021 Between each terminals*1 and ground terminal
500V AC for one minute
Insulation resistance*1
5MΩ or more by
500V DC megge
Grounding
Class D grounding (grounding resistance: 100 Ω or
less)
system is not allowed.>*2
Working atmosphere
Free from corrosive or flammable gas and excessive conductive dusts
Working altitude
Compliant with IEC61131-2 (<2000m)*3
*1
Terminal
Dielectric strength
Insulation resistance
Between power supply
terminal (AC power) and
ground terminal
1.5 kV AC for
one minute
5MΩ or more by
500V DC megger
Between power supply
terminal (DC power) and
ground terminal
500V AC for
one minute
Between input terminal
(24V DC) and ground
terminal
500V AC for
one minute
Between output terminal
(relay) and ground
terminal
1.5 kV AC for
one minute
Between output terminal
(transistor) and ground
terminal
500V AC for
one minute
For dielectric with stand voltage test and insulationresistance test of each product, refer to the following manual.
→ Refer to FX3U Series User's Manual - Hardware Edition.
*2 For common grounding, refer to section 3.3.
*3 The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
No comment |