No comment |
>
Control System >
PLC >
Mitsubishi PLC >
FX2N-485-BD Mit RS-485 serial communications adapter Module NewFX2N-485-BD Mit RS-485 serial communications adapter Module New
Introduction
The communication board FX2N-485-BD for RS485 (hereinafter referred to as “485BD”) can be connected to the base unit of the Fx2N series PC to be used for the following applications.
1, Data transfer using the no protocol
Data communication with diversified RS232C units including personal computers, bar code readers and printers can be performed via the RS485(422) converter using the no protocol. In this application, data is sent or received using the data registers specified bu the RS instruction because the 485BD does not have a buffer memory. For the setting and program examples.
2, Data transfer using the dedicated protocol
Data transfer with RS485(422) units can be performed on the 1;N basis using the dedicated protocol. For the contents of the dedicated protocol used in the application
3, Data transfer using the parallel link
Data transfer with an Fx2N programmable controller can be performed on the 1:1 basis for 100 auxiliary relays and 10 data registers
4, Data transfer using the N:N network
Data transfer with FX2N programmable controllers can be performed on the N:N basis.
General Specification
General specifications is same as those for the FX2N series programmable controller.
Power Supply Specification
5VDC, 60mA is supplied as the power from the programmable controller.
Specification
Transmission standard
Conforming to RS485 and RS422
Transmission distance
Max. 50m
LED indicators
SD, RD
Communication method
Half-duplex communication system
Protocol
Dedicated protocol(format 1 or format 4), No protocol, Parallel link, N:N network
Isolation
No isolation
External Dimensions