No comment |
CPU61 Omron PLC CQM1H-Omron PLC New in boxOmron PLC CQM1H-CPU61
Product Description?
The CQM1H’s rack-less modular design lets you customize your control system by adding “inner boards” for advanced functions, as well as specialized I/O and communications modules. CQM1H offers the most flexibility of all PLC systems in its class.
D 4 different base CPUs to choose from; 16 DC inputs built in; expands up to 512 points
D No separate backplane required
D Inner Boards allow “customized” configuration of the CPU
D Serial communications inner board supports protocol macro feature for communication with third-party serial devices
D Supports all existing and new CQM1 I/O and specialized I/O modules
D Optional memory cassettes allow backup of sensitive data, provides a real-time clock
D ControllerLink network transmits 8 kword data packets at up to 2 Mbps; 32 nodes
D Advanced instruction set includes PID, floating point math, protocol macro instructions and more
D CompoBus/S, SYSMAC BUS and AS-interface masters support remote I/O
D Up to 15.2 kwords of program memory
Features:
Item
CQM1-PA203
CQM1-PA206
CQM1-PA216
CQM1-PD026
Supply voltage
100 to 240 VAC, 50/60 Hz
100 or 230 VAC (selectable), 50/60 Hz
24 VDC
Operating voltage range
85 to 264 VAC
85 to 132 VAC or 170 to 264 VAC
20 to 28 VDC
Operating frequency range
47 to 63 Hz
—
Power consumption
60 VA max.
120 VA max.
50 W max.
Inrush current
30 A max.
Output capacity
5VDC: 3.6A(18W)
5 VDC: 6 A 24 VDC: 0.5 A (30 W total)
5 VDC: 6 A (30 W)
Insulation resistance
20 M? min. at 500 VDC between AC external terminals and GR terminals
Dielectric strength
2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals, leakage current: 10 mA max. 1,000 VAC 50/60 Hz for 1 min between DC external and GR terminals, leakage current: 20 mA max.
Noise immunity
Conforms to IEC61000-4-4, 2 kV (power lines)
Vibration resistance
10 to 57 Hz with an amplitude of 0.075 mm, and 57 to 150 Hz with an acceleration of 9.8 m/s2 in the X,Y,and Z directions for 80 minutes each (i.e., swept for 8 minutes, 10 times).
Shock resistance
147 m/s2 (118 m/s2 for Contact Output Units) 3 times each in X, Y, and Z directions
Ambient temperature
Operating: 0° to 55°C(32° to 131°F) Storage: -20? to 75?(-4° to 167°F), except battery)
Ambient operating humidity
10% to 90% RH (no condensation)
Operating environment
No corrosive gas
Ground
Less than 100 ?
Construction
Panel mounted
Weight
5kgmax.
Internal current consumption
CQM1H-CPU11: 820 mA at 5 VDC CQM1H-CPU21/51/61: 840 mA at 5 VDC
Dimensions (without cables)
CQM1H-CPU11/21: 187 to 571 ¢ 110 ¢ 107 mm (W¢H¢D) CQM1H-CPU51/61: 187 to 603 ¢ 110 ¢ 107 mm (W¢H¢D)
Accessories
RS-232C connector (one XM2A-0901 Plug and one XM2S-0911-E Hood) (except CQM1H-CPU11) CPM2A-BAT01 Battery Set (installed in CPU Unit when shipped)
Note: The total power consumed at 5 VDC and 24 VDC must be less than 30 W. (5 × Current consumed at 5 VDC) + (24 × Current consumed at 24 VDC) ≤ 30 W
No comment |