No comment |
>
Control System >
PLC >
Mitsubishi PLC >
FX-485PC-IF FX series Mitsubishi PLC Interface Unit RS485 Original Brand NewFX-485PC-IF FX series Mitsubishi PLC Interface Unit RS485 Original Brand New
Introduction
The 485PC-IF has an RS-232C port for connection with computer, and an RS-485 terminal block for connection with the PC, and is designed as an interface unit for converting the RS-232C signal of the computer into an RS-485 signal.
A dedicated protocol is used in the transmission control procedure for linking the PC and the computer. The transmission data of the dedicated protocol is communicated in ASCII code as shown below.
Environment specifications
Ambient temperature
Operating: 0 to 550C, storing: -20 to 700C
Ambient humidity
Operating: 35 to 85% (with no condensation)
Vibration resistance
Conforming to JIS C 0911: 10 to 55Hz, 0.5mm (max 2G), 2 hours each in 3 axes.
Shock resistance
Conforming to JIS C 0912: 10 G. 3 times each in 3 axes.
Noise immunity
Noise voltage 1000 Vp-p, noise width 1 u sec, period 30 to 100Hz, by noise simulator.
Withstand Voltage
500VAC, 1 min
Between terminals in batch and case
Insulation resistance
5m ohm or more by 500 VDC megger
Operating ambience
Free from corrosive gas, minimal dust.
Power source specifications of 485PC-IF
Power source
5 VDC+-5%
Current consumption
Max. 250mA