System Overview
A basic MicroLogix 1500 system consists of a base unit that provides 24 or 28 built-in basic I/O, a built-in AC or DC power supply, and a processor module that slides into the base unit. You can supplement the I/O built into the base unit with up to sixteen digital and/or analog input and output 1769 Compact™ I/O modules (depending on current draw and power dissipation). Add an optional memory and/or real-time clock module or an optional Data Access Tool to enhance system capability.General Specifications
These specifications cover the base unit, the processor module, real-time-clock/memory module, and data access tool.
Nonoperating Temperature
-40…85 °C (-40…185 °F)
Operating Temperature
0…55 °C (32…131 °F)
Operating Humidity
5…95% (without condensation)
Operating Altitude
2,000 m (6,561 ft) max.
Vibration
Operating
10…500 Hz, 5g, 0.030 inch maximum peak-to-peak
Relay Operation
2g
Shock (Without Data Access Tool installed)
Operating
30g panel mounted (15g DIN Rail mounted)
Relay Operation
7.5g panel mounted (5g DIN Rail mounted)
Non-Operating
40g panel mounted (30g DIN Rail mounted)
Shock (With Data Access Tool installed)
Operating
20g panel mounted (15g DIN Rail mounted)
Relay Operation
7.5g panel mounted (5g DIN Rail mounted)
Non-Operating
30g panel mounted (20g DIN Rail mounted)
Weight
0.9 kg (2.0 lb)
Agency Certification
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directivesHazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions
EN50081-2 Class A
Electrical and EMC:
The module has passed testing at the following levels:
ESD Immunity (IEC1000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated immunity (IEC1000-4-3)
10V/m, 80…1000 MHz, 80% amplitude modulation, +900 MHz keyed carrier
Fast Transient Burst (IEC1000-4-4)
2 kV, 5 kHz
Surge Immunity (IEC1000-4-5)
2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC1000-4-6)
10V, 0.15…80 MHz?
Conducted immunity frequency range may be 150 kHz…30 MHz if the radiated immunity frequency range is 30 MHz…1000 MHz.