No comment |
>
Control System >
PLC >
AB PLC >
1762-IQ16 AB Allen-Bradley PLC 24VDC 16 Input Points Digital Input Module 1762 Series Original brand new1762-IQ16 AB PLC 24VDC 16 Input Points Digital Input Module 1762 Series Original brand new
1762 MicroLogix Expansion I/O
The 1762 MicroLogix expansion I/O modules are compatible with MicroLogix 1100, MicroLogix 1200, and MicroLogix 1400 controllers. If your application requires more I/O than the built-in I/O provided by the controller, add expansion I/O modules.
Integrated high-performance I/O busSoftware keying to prevent incorrect positioning within the systemFinger-safe terminal blocks for I/O wiringLabel to record I/O terminal designationsNetwork support includes EtherNet/IP, DeviceNet, and DH-485 (local only)Digital, analog, and specialty I/O modules available
Install the expansion I/O modules to the right of the controller, either on a panel with two mounting screws or on a DIN rail. You can use digital and analog I/O modules in many combinations, up to the maximum supported by the controller. The current loading capacity of the controller’s built-in power supply may limit the actual number of I/O modules that can be connected to the controller.
FeaturesDigital Input Modules
Cat. No.
Inputs
Voltage Category
Operating Voltage Range
On-State Current, Max.
Impedance, Nom.
Signal Delay, Max.
Off-State Voltage and Current, Max.
Bus Current Draw, Max.
1762-IA8
8
100/120V AC
79…132V AC at 47…63 Hz
16 mA at 132V AC, 63 Hz
12 kW at 50 Hz
10 KW at 60 HzOn/Off: 20 ms
20V AC
2.5 mA50 mA at 5V DC (0.25 W)
1762-IQ8
8
24V DC sink/source
10…26.4V DC at 55 °C (131 °F)
10…30V DC at 30 °C (86 °F)12 mA at 30V DC
3 kW
On/Off: 8 ms
5V DC
1.5 mA50 mA at 5V DC (0.25 W)
1762-IQ16
16 (8 points/group)
24V DC sink/source
10…26.4V DC
10…30V DC? ‡12 mA at 30V DC
3 kW
On/Off: 8 ms
5V DC
1.5 mA70 mA at 5V DC (0.35 W)‡
1762-IQ32T
32 (8 points/group)
24V DC sink/source
10…26.4V DC
10…30V DC§6.5 mA at 30.0V DC
4.7 kW
On/Off: 8.0 ms
5V DC
1 mA170 mA at 5V DC
? See MicroLogix 1762-IQ16 DC Input Module Installation Instructions, publication 1762-IN010, for derating chart.
§ See MicroLogix 1762-IQ32T DC Input Module Installation Instructions, publication 1762-IN019, for derating chart.
‡ Only applicable for series B.