No comment |
>
Control System >
PLC >
AB PLC >
1746-OV8 AB PLC 10-50V DC sink General-purpose DC outputs 1746 Series Original brand new1746-OV8 AB PLC 10-50V DC sink General-purpose DC outputs 1746 Series Original brand new
Features
Hardware-platform sharing makes spare-parts stocking convenient.Combinations of input and outputs in the same digital and analog modules provide expansion capabilities without sacrificing space or increasing cost.Variety of voltages creates a precise power fit for your application.No need to disconnect wiring to replace module of 16 or more I/O; removable terminal blocks are shipped with I/O modules.Broad range of signal interfaces to AC and DC sensors/actuators for a wide variety of applications.LED indicators show input/output status for easier troubleshooting.Modules available in different densities (32 I/O per module max) for greater flexibility and cost savings.1746 I/O modules include optical coupling and filter circuitry for signal noise reduction.A wide range of analog signal levels including standard analog inputs and outputs, and direct thermocouple and RTD temperature inputs.1746 Digital DC Output Modules
Cat. No.
Operating Voltage
Continuous
Current per Output, Max.Continuous
Current/Module, Max.Number of Outputs
Backplane Current Load
Applications
1746-OB6EI
10 …30V DC
source2.0 A at 0…60 °C
12 A at 0…60 °C
6
46 mA at 5V
Individually isolated electronically fused DC outputs that automatically reset
1746-OB8
10…50V DC
source1.0 A at 30 °C
0.5 A at 60 °C8 A at 30 °C
4 A at 60 °C8
135 mA at 5V
General-purpose DC outputs
1746-OV8
10…50V DC
sink1.0 A at 30 °C
0.5 A at 60 °C8 A at 30 °C
4 A at 60 °C8
135 mA at 5V
General-purpose DC outputs
1746-OB16
10…50V DC
source0.50 A at 30 °C
0.25 A at 60 °C8 A at 30 °C
4 A at 60 °C16
280 mA at 5V
General-purpose DC outputs
1746-OB16E
10…30V DC
source1.00 A at 30 °C
0.50 A at 60 °C8 A at 0…60 °C
16
135 mA at 5V
Electronically fused DC outputs that automatically reset
1746-OV16
10…50V DC sink
0.5 A at 30 °C
0.25 A at 60 °C8 A at 30 °C
4 A at 60 °C16
270 mA at 5V
General-purpose DC outputs
1746-OBP8
20.4…26.4V DC
source2.0 A at 60 °C
8.0 A at 0…60 °C
8
135 mA at 5V
High-current DC source output
1746-OBP16
20.4…26.4V DC
source1.5 A at 30 °C
1.0 A at 60 °C6.4 A at 0…60 °C
16
250 mA at 5V
High-current DC source output
1746-OVP16
20.4…26.4V DC
sink1.5 A at 30 °C
1.0 A at 60 °C6.4 A at 0…60 °C
16
250 mA at 5V
High-current DC sink output, fused common
1746-OG16
5V DC
sink0.024 A
0.384 A
16
180 mA at 5V
TTL loads; sink-load display devices
1746-OB32
5…50V DC
source0.5 A at 30 °C
0.2 A at 60 °C8.0 A at 0…60 °C
32
190 mA at 5V
High-density low-current DC outputs
1746-OB32E
10…32V DC
source0.5 A at 30 °C
0.25 A at 60 °C8.0 A at 0…60 °C
32
190 mA at 5V
Electronically fused DC outputs that automatically reset
1746-OV32
5…50V DC sink
0.5 A at 30 °C
0.25 A at 60 °C8.0 A at 0…60 °C
32
190 mA at 5V
High-density low-current DC outputs
No comment |