1747-M13 Rockwell PIC SLC500 serial NEW

prevnext

1747-M13 Rockwell PIC SLC500 serial NEW
  • Market price: $ 874.5
  • Shop price: $ 265.0
  • Goods click count: 186
  • Total:
  • Quantity:
Add to cart collect
  

Description

1747-M13 Rockwell PIC SLC500 serial NEW

If you need more than 10pcs and want to get better wholesale price, please feel free to contact us by following:
email:[email protected]
Tel:0086-574-88333153
We will quote you our best price to you in 24hours.

The SLC 500 was one of the first full-featured, small controllers on the market, and it remains the gold standard in small logic controllers more than a decade after its introduction. It’s a rugged chassisbased platform, which means you can configure exactly the stand-alone or distributed system you need for dependable control of your application.

In fact, the SLC 500 provides cost-efficient, reliable control in hundreds of thousands of applications around the world — everything from amusement park rides and microbreweries to pharmaceutical and food processes.

Product features:

*The Small Controller for Big Applications

*Protecting Your Control Investment

*Meeting Changing Times Head-on

Product specification:

Specification

SLC 5/01

SLC 5/02

SLC 5/03

SLC 5/04

SLC 5/05

Catalog Number 1747-

L511

L514

L524

L531

L531 L532

L541

L542

L543

L551

L552

L553

Memory Size (Words)

1K

4K

4K

8K

16K

16K

32K

64K

16K

32K

64K

Backplane Current (mA) at 5V

350 mA

500 mA

1000 mA

Backplane Current (mA) at 24V

105 mA

175 mA

0 mA

Digital I/O, Max.

7880

8192

Max. Local Chassis/Slots

3/30

On-Board Communications

DH-485 Slave

DH-485

DH-485 and RS-232

DH+ and RS-232

10/100 Mbps Ethernet
and RS-232

Optional Memory Module

EEPROM

Flash EEPROM

Programming

RSLogix 500

Programming Instructions

52

71

107

Typical Scan Time*

8 ms/K

 

4.8 ms/K

1 ms/K

 

0.9 ms/K

 

 

 

 

 

Program Scan Hold-up Time
After Loss of Power

20 ms…3 s (dependent on power supply loading)

Bit Execution (XIC)

4 μs

2.4 μs

0.44 μs

0.37 μs

Clock/Calendar Accuracy

N/A

±54 seconds/month @ +25 °C (+77 °F), ±81 seconds/month @ +60 °C (+140°F)

*The scan times are typical for a 1K ladder logic program consisting of simple ladder logic and communication servicing.

Actual scan times depend on your program size, instructions used, and the communication protocol.

 






  