Rockwell SLC 500 Power Supplies 1746-P4

 

General Specifications:

Attribute

Value

1746-P1

1746-P2

1746-P3

1746-P4

Line voltage

85...132/170...265V ac
47...63 Hz

19.2...28.8V dc

85...132/
170...250V ac 47...63 Hz

Typical line power
requirement

135VA

180VA

90VA

150VA

Inrush current, max

20 A

45 A

Internal current
capacity

2 A at 5V dc
0.46 A at 24V dc

5 A at 5V dc
0.96 A at 24V dc

3.6 A at 5V dc
0.87 A at 24V dc

10.0 A at 5V dc
2.88 A at 24V dc(1)

Fuse protection(2)

1746-F1 or
equivalent(3) (4)

1746-F2 or
equivalent(3) (5)

1746-F3 or
equivalent(3) (6)

Fuse is soldered in
place.

24V dc user-power
current capacity

200 mA

Not applicable

1 A(1)

24V dc user-power
voltage range

18...30V dc

20.4...27.6V dc

User-supplied
overcurrent
protection(7), max

15 A

Not applicable

15 A

Temperature,
ambient operating

0...60 °C (32...140 °F)
Current capacity is derated 5% above 55 °C (131 °F).

0...60 °C
(32...140 °F)
no derating

Isolation(8)

1800V ac RMS for 1 s

600V ac RMS for 1 s
(version B or later)

2600V dc for 1 s

CPU hold-up time(9)

20 ms (full load) 3000 ms (no load)

5 ms (full load)
1000 ms (no load)

20 ms (full load)
3000 ms (no load)

Certification
(when product is
marked)

UL Listed Industrial Control Equipment for Class 1, Division 2,
Groups A, B, C, D Hazardous Locations

UL Listed Industrial
Control Equipment

C-UL Listed Industrial Control Equipment for Class 1, Division 2,
Groups A, B, C, D Hazardous Locations

CSA Certified
Process Control
Equipment for
Class 1, Div 2,
Groups A, B, C, D
Hazardous Locations

CE(10)
European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2 Industrial Immunity
EN50081-2 Industrial Emissions
European Union 73/23/EEC LVD Directive, compliant with:
EN61131-2 Programmable Controllers

C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS 2064 Industrial Emissions

(1) The combination of all output power (5V backplane, 24V backplane, and 24V user source) cannot exceed 70 W.

(2) Power supply fuse is intended to guard against fire hazard due to short-circuit conditions. This fuse may not protect the supply from miswiring or excessive transient in the power line.

(3) Fuse sizes specified are for end-devices only. Fuse size may need to be reduced depending on the size of circuit wiring.

(4) Equivalent fuses: 250V-3A fuse, nagasawa ULCS-61ML-3, or BUSSMAN AGC 3.

(5) Equivalent fuse: 250V-3A fuse, SANO SOC SD4, or BUSSMAN AGC 3.

(6) Equivalent fuse: 125V-5A fuse, LITTLEFUSE 233.

(7) Use time-delay type overcurrent protection in all ungrounded conductors.

(8) Isolation is between input terminals and backplane.

(9) CPU hold-up time is for 0V unless specified. Hold-up time is dependent on power supply loading.

(10) See the Product Certification link at http://ab.com for Declarations of Conformity, Certificates, and other certification details.

 
































  