SLC 500 controllers continue to operate (hold-up) for a short period of time if the input voltage to the power supply drops below the recommended operating voltage range. The controller continues to scan the user program and control I/O during this time. CPU hold-up for each power supply is shown on pages 14 and 16.SLC 500 controllers turn OFF (stop scanning and disable outputs) if input voltage to the power supply is removed or drops below the recommended operating range for a period exceeding the CPU hold-up time. The controller resumes operation automatically when the input voltage is restored to normal.
If the input voltage to the 1746-P7 power supply falls into a range of 4 to 9V for a period exceeding the CPU hold-up time, the controller turns OFF and will not turn back ON until input voltage is increased to 11V dc.
General Specifications (1746-P1, 1746-P2, 1746-P3, and 1746-P4)
Attribute
Value
1746-P1
1746-P2
1746-P2
1746-P2
Line voltage
85...132/170...265V ac
47...63 Hz
19.2...28.8V dc
85...132/
170...250V ac 47...63
Hz
Typical line power
requirement
135VA
180VA
90VA
150VA
Inrush current, max
20A
Internal current
capacity
2 A at 5V dc
0.46 A at 24V dc
5 A at 5V dc
0.96 A at 24V dc
3.6 A at 5V dc
0.87 A at 24V dc
10.0 A at 5V dc
2.88 A at 24V dc
Fuse protection
1746-F1 or
equivalent
1746-F2 or
equivalent
1746-F3 or
equivalent
Fuse is soldered in
place.
24V dc user-power
current capacity
200 mA
Not applicable
1 A
24V dc user-power
voltage range
18...30V dc
20.4...27.6V dc
User-supplied overcurrent protection, max
15 A
Not applicable
15 A
Temperature, ambient operating
0...60 °C (32...140 °F)
Current capacity is derated 5% above 55 °C (131 °F).
0...60 °C
(32...140 °F)
no derating
Isolation
1800V ac RMS for 1 s
600V ac RMS for 1 s
(version B or later)
2600V dc for 1 s
CPU hold-up time
20 ms (full load) 3000 ms (no load)
5 ms (full load)
1000 ms (no load)
20 ms (full load)
3000 ms (no load)