No comment |
>
Control System >
PLC >
Delta PLC >
DVPPF02-H2 Delta PLC PROFIBUS DP slave communication module Original brand newDVPPF02-H2 Delta PLC PROFIBUS DP slave communication module Original brand new
Introduction
1. To ensure correct installation and operation of DVPPF02-H2, please read this chapter carefully before using your DVPPF02-H2.
2. This chapter provides only introductory information on DVPPF02-H2. Details of PROFIBUS DP protocol are not included in this sheet. For more information on PROFIBUS DP protocol, please refer to relevant references or literatures.
3. DVPPF02-H2 is a PROFIBUS DP slave communication module, connecting DVP-EH2 series PLC to PROFIBUS DP network.
Features
1. Supports loop-type data exchange between PROFIBUS DP master and many slaves.
2. The length of I/O data can be freely configured through PROFIBUS DP network configuration tools. Max. input data length = 100 words (the sum of 4 slots); Max.output data length = 100 words (the sum of 4 slots).
3. Supports GSD files in PROFIBUS DP network configuration tool.
4. Supports 4 slots in PROFIBUS DP network configuration tool.
5. Auto-detects baud rates; supports Max. 12M bps.
Specifications
ƒ PROFIBUS DP connector
Transmission method
High-speed RS-485
Electrical isolation
500VDC
Interface
DB9 connector
Transmission cable
Shielded twisted pair cable
Communication
Message type
DPV0, loop-type data exchange
Equipment ID
0AFE (hex)
GSD file
DELT0AFE.GSD
Module name
DVPPF02-H2
Transmission speed
(Auto-detect)
9.6 kbps 19.2 kbps 93.75 kbps 187.5 kbps 500 kbps 1.5 kbps 3 Mbps 6 Mbps 12 Mbps
Environment
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Operation/storage
Operation: 0°C ~ 55°C (temperature), 50% ~ 95% (humidity), pollution
degree 2
Storage: -25°C ~ 70°C (temperature), 5% ~ 95% (humidity)
Vibration/shock
immunity
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27
(TEST Ea)
Certificates
IEC 61131-2, UL508
Product Profile
No comment |