Your Position: Home > Control System > PLC > AB PLC > 1746-NT8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Input 16 Bits New

  Categories

Control System
Motion Control System
LCD Screen Panel
Instrumentation
Low Voltage
Transducer/Sensor
  

Service



Email: [email protected]
Tel: 0086-574-88333153

View History

   

1746-NT8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Input 16 Bits New

prevnext

1746-NT8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Input 16 Bits New
  • Market price: $ 4653.0
  • Shop price: $ 1410.0
  • Goods click count: 238
  • Total:
  • Quantity:
Add to cart collect
  

Description

1746-NT8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Input 16 Bits New

If you need more than 10pcs and want to get better wholesale price, please feel free to contact us by following:
email:[email protected]
Tel:0086-574-88333153
We will quote you our best price to you in 24hours.

PLCAGE: 1746-NT8 Allen-Bradley PLC 1746 RTD and Thermocouple Modules 8 Input 16 Bits New

Features

This module mounts into 1746 I/O chassis for use with SLC 500 fixed and modular systems. The module stores digitally converted thermocouple/mV analog data in its image table for retrieval by all fixed and modular SLC 500 processors. The module supports connections from any combination of up to eight thermocouple/mV analog sensors.

Specification

Backplane Current Consumption

120 mA at 5V dc

70 mA at 24Vd

Backplane Power Consumption

2.28W maximum (0.6W at 5V dc, 1.68W at 24V dc)

Number of Channels

8 (backplane and channel-to-channel isolated)

I/O Chassis Location

Any I/O module slot except 0

A/D Conversion Method

Sigma-Delta Modulation

Input Filtering

Input Filtering Low pass digital filter with

programmable notch (filter) frequencies

Normal Mode Rejection (between [+]

input and [-] input)

Greater than 100 dB at 50/60 Hz

Common Mode Rejection (between

input and ground)

Greater than 100 dB at 50/60 Hz

nput Filter Cut-Off Frequencies

2.6 Hz at 10 Hz filter frequency

13.1 Hz at 50 Hz filter frequency

15.72 Hz at 60 Hz filter frequency

65.5 Hz at 250 Hz filter frequency

 

 

Greater than 100 dB at 50/60 Hz

Calibration

Module autocalibrates at power-up and

approximately every two minutes afterward

 

Input Over-voltage Protection

±30V dc continuous 600W pulsed for 1 ms

 

Isolation

500V dc for 1 minute between inputs and chassis

ground and between inputs and backplane. 12.5V

dc continuous between channels.

 

  