No comment |
>
Control System >
PLC >
Delta PLC >
PLC DC24V 8 DI 4 AI 6 DO 2 AO transistor PNP Delta DVP20SX211S NewDVP20SX211S Delta PLC 24VDC 8(4AI) 6(2AO) transistor(PNP) output Analog Original brand new
Features
The 2nd generation DVP-SX2 series slim type PLC offers 14 digital points and built-in 12-bit analog I/O points. It is extendable with DVP-S series left-side and right-side extension modules.
Specifications
*MPU points: 20 (8DI/6DO, 4AI/2AO)
*Max. I/O points: 494 (14 + 480)
*Program capacity: 16k steps
*COM port: Built-in RS-232, RS-485 & USB ports, compatible with ASCII/RTU protocol. Can be master or slave.
*High-Speed Pulse Output: Supports 2 points (Y0, Y2) of 100kHz and 2 points (Y1, Y3) of 10kHz independent high-speed pulse output.
*Built-in High-Speed Counters
Model
Item
DVP20SX211R
DVP20SX211T
DVP20SX211S
Power supply voltage
24 VDC (-15 to 20%)
(with counter-connection protection on the polarity of DC input power)
DVPPS01/PS02: input 100 to 240 VAC, output 24 VDC/1A (PS02: 2A)
Inrush current
Max. 7.5 A@24 VDC
Fuse capacity
2.5 A/30 VDC, Polyswitch
Power consumption
4.7W
4W
4W
Insulation resistance
> 5 M Ohm (all I/O point-to-ground: 500 VDC)
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N (All DVP units should be grounded directly to the ground pole).
Operation / storage
Operation: 0 to 55°C (temp.), 50 to 95% (humidity), Pollution degree 2
Storage: -25 to 70°C (temp.), 5 to 95% (humidity)
Vibration / shock resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST
Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Weight (g)
243
224
227
Applications
Used for PID temperature/humidity control, 2-axis AC motor drive constant speed control, temperature control using a analog signal monitoring of a whole factory. (PLC EASY LINK)
No comment |