No comment |
>
Control System >
PLC >
Schneider PLC >
BMXDDM3202K Schneider PLC Discrete I/O Module M340 16 Inputs 24VDC 16 Outputs Solid State NEWBMXDDM3202K Schneider PLC Discrete I/O Module M340 16 Inputs 24VDC 16 Outputs Solid State NEW
Main
Range of product | Modicon M340 automation platform |
Product or component type | Discrete I/O module |
Discrete input number | 16 |
Discrete input voltage | 24 V DC positive |
Input compatibility | With 2-wire/3-wire proximity sensors IEC 60947-5-2 |
Discrete output number | 16 |
Discrete output type | Solid state |
Discrete output voltage | 24 V , : 19...30 V DC |
Ambient air temperature for operation | 0...60 °C |
Protective treatment | TC |
Complementary
Electrical connection | 20-way connector |
Input type | Current sink (logic positive) |
Discrete input current | 2,5 mA |
Discrete output current | 0,1 A |
Sensor power supply | 19...30 V |
Voltage state 1 guaranteed | ≥ 11 V |
Current state 1 guaranteed | ≥ 2 mA |
Voltage state 0 guaranteed | ≤ 5 V |
Current state 0 guaranteed | ≤ 1,5 mA |
Current per channel | ≤ 0,125 A |
Current per module | ≤ 3,2 A |
Leakage current | ≤ 0,1 mA at state 0 |
[Ures] residual voltage | ≤ 1,5 V at state 1 |
Input impedance | 9600 Ohm |
Insulation resistance | > 10 MOhm 500 V DC |
Power dissipation in W | ≤ 4 W |
DC typical filtering time | 4 ms |
DC maximum filtering time | 7 ms |
Response time on output | 1,2 ms |
Paralleling of outputs | Yes : 3 maximum |
Typical current consumption | 69 mA 24 V DC |
Current consumption | ≤ 104 mA 24 V DC |
MTBF reliability | 432904 h |
Protection type | 1 external fuse per group of input channel 0,5 A fast blow |
Output overload protection | With current limiter |
Output overvoltage protection | With transil diode |
Output short-circuit protection | With 2 A external fuse |
Reverse polarity protection | Reverse mounted diode |
Voltage detection threshold | < 14 V DC sensor , fault |
Tungsten load | ≤ 1,2 W |
Switching frequency | 0.5/LI² Hz |
Overload time | ≤ 15 ms |
Load impedance ohmic | ≤ 220 Ohm |
Status LED | 1 LED green module operating (RUN) |
Product weight | 0,11 kg |
Environment
IP degree of protection | IP20 |
Standards | CSA 22-2 No 142 |
Dielectric strength | 500 V DC 1 minute, between group of inputs and outputs |
Relative humidity | 10...95 % without condensation |
RoHS EUR conformity date | 0722 |
RoHS EUR status | Compliant |
BMXDDM3202K Schneider PLC Discrete I/O Module M340 16 Inputs 24VDC 16 Outputs Solid State NEW
Main
Range of product
Modicon M340 automation platform
Product or component type
Discrete I/O module
Discrete input number
16
Discrete input voltage
24 V DC positive
Input compatibility
With 2-wire/3-wire proximity sensors IEC 60947-5-2
Discrete output number
16
Discrete output type
Solid state
Discrete output voltage
24 V , : 19...30 V DC
Ambient air temperature for operation
0...60 °C
Protective treatment
TC
Complementary
Electrical connection
20-way connector
Input type
Current sink (logic positive)
Discrete input current
2,5 mA
Discrete output current
0,1 A
Sensor power supply
19...30 V
Voltage state 1 guaranteed
≥ 11 V
Current state 1 guaranteed
≥ 2 mA
Voltage state 0 guaranteed
≤ 5 V
Current state 0 guaranteed
≤ 1,5 mA
Current per channel
≤ 0,125 A
Current per module
≤ 3,2 A
Leakage current
≤ 0,1 mA at state 0
[Ures] residual voltage
≤ 1,5 V at state 1
Input impedance
9600 Ohm
Insulation resistance
> 10 MOhm 500 V DC
Power dissipation in W
≤ 4 W
DC typical filtering time
4 ms
DC maximum filtering time
7 ms
Response time on output
1,2 ms
Paralleling of outputs
Yes : 3 maximum
Typical current consumption
69 mA 24 V DC
125 mA 3.3 V DCCurrent consumption
≤ 104 mA 24 V DC
≤ 166 mA 3.3 V DCMTBF reliability
432904 h
Protection type
1 external fuse per group of input channel 0,5 A fast blow
Overvoltage protection on output
Reverse polarity protection on input
Reverse polarity protection on outputOutput overload protection
With current limiter
With electronic circuit breaker 0.125 A < Id < 0.185 AOutput overvoltage protection
With transil diode
Output short-circuit protection
With 2 A external fuse
Reverse polarity protection
Reverse mounted diode
Voltage detection threshold
< 14 V DC sensor , fault
< 14 V DC preactuator , fault
> 18 V DC sensor , OK
> 18 V DC preactuator , OKTungsten load
≤ 1,2 W
Switching frequency
0.5/LI² Hz
Overload time
≤ 15 ms
Load impedance ohmic
≤ 220 Ohm
Status LED
1 LED green module operating (RUN)
1 LED red module error (ERR)
1 LED red module I/O
1 LED per channel green channel diagnosticProduct weight
0,11 kg
Environment
IP degree of protection
IP20
Standards
CSA 22-2 No 142
IEC 1131-2
IEC 664
NF C 63-850
UL 508
UL 746CDielectric strength
500 V DC 1 minute, between group of inputs and outputs
1500 V AC 50/60 Hz 1 minute, primary/secondary
1500 V AC 50/60 Hz 1 minute, output/ground
1500 V AC 50/60 Hz 1 minute, output/internal logicRelative humidity
10...95 % without condensation
RoHS EUR conformity date
0722
RoHS EUR status
Compliant
No comment |