DVP12SS211S Delta PLC 24VDC 8DO 4DO transistor(PNP) Standard Original brand newDVP12SS211S Delta PLC 24VDC 8DO 4DO transistor (PNP) Standard Original brand new
Features
The 2nd generation DVP-SS2 series slim type PLC keeps the basic sequential control functions from the DVP-SS series PLC but with faster execution speed and enhanced real-time monitoring capability.
Specifications
*MPU points: 14 (8DI + 6DO)
*Max. I/O points: 494 (14 + 480)
*Program capacity: 8k steps
*COM port: Built-in RS-232 & RS-485 ports, compatible with Modbus ASCII/RTU protocol. Can be master or slave.
*High-Speed Pulse Output: Supports 4 points (Y0 ~ Y3) of independent high-speed (max. 10kHz) pulse output
*Supports PID Auto-tuning: DVP-SS2 saves parameters automatically after the PID auto temperature tuning is completed.
*Built-in High-Speed Counters
Model
Item
DVP14SS211R
DVP14SS211T
DVP12SS211S
Power supply voltage
24 VDC (-15 to 20%)
(with counter-connection protection on the polarity of DC input power)
DVPPS01/PS02: input 100 to 240 VAC, output 24 VDC/1A (PS02: 2A)
Inrush current
Max. 7.5 A@24 VDC
Fuse capacity
1.85 A/30 VDC, Polyswitch
Power consumption
1.8W
1.5W
Power protection
With counter-connection protection on the polarity of DC input power
Insulation resistance
> 5 M Ohm (all I/O point-to-ground: 500 VDC)
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire
diameter of terminals L and N (All DVP units should be grounded
directly to the ground pole).
Operation / storage
Operation: 0 to 55°C (temp.), 50 to 95% (humidity), Pollution degree 2
Storage: -25 to 70°C (temp.), 5 to 95% (humidity)
Vibration / shock resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST
Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Weight (g)
97
82.5
90