DVP08XP11R Delta PLC 4DI 4DO relay output Digital Module Original brand newDVP08XP11R Delta PLC 4DI 4DO relay output Digital Module Original brand new
Introduction
The DVP series provides different extension units with specific I/O (please refer to Section 1.1 for specifications). The total input and output points can extend to 256 points. If 256 points are exceeded, the ERROR LED of the MPU will flash.
General Specification
Models
Items
DVP08XN11
DVP08XP11R
DVP08XM11N
DVP16XM01N
DVP-16XN01
DVP24XP01
DVP24XN01
DVP32XP01
DVP24XP00
DVP24XN00
DVP32XP00
Power Supply Voltage
24VDC (-15%~20%)
100~240VAC (-15%~20%)
50/60Hz +- 5%
Fuse Capacity
2A/250VAC
Power consumption (MAX)
5W
5W
6.5W
6.5W
8W
30VA
DC24V supply current
--
--
--
--
--
400mA
Power Protection
--
DC24V output with
short-circuit protection
Withstand Voltage
1500VAC(Primary-secondary)1500VAC(Primary-PE)500VAC(Secondary-PE)
Retentive Power Interruption
Continues operation within 5ms
Continues operation within
10ms
Insulation Resistance
>5 M at 500VDC (Between all inputs/outputs and earth)
Noisy Immunity
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz~1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N (All DVP units should be grounded directly to the ground pole).
Operation/Storage
Environment
Operation: 0~55 (Temperature), 50~95% (Humidity); Storage: -25~70 (Temperature), 5~95% (Humidity) Pollution degree 2
Vibration /Shock resistance
Standard IEC1131-2, IEC 68-2-6[1]TEST Fc
/ IEC1131-2 & IEC 68-2-27 (TEST Ea)
Weight (g)
170/165
160/270
280
434
462/442
600/580