TM200HSC206DF Modicon M238 logic controller 60 kHz 2 Spring Terminal Blocks Brand NEWTM200HSC206DF Modicon M238 logic controller 60 kHz 2 Spring Terminal Blocks Brand NEW
TM200HSC206DF Modicon M238 logic controller - 4 O discrete - 60 kHz - 2 spring terminal blocks.
Main
Range of product
Modicon M238 logic controller
Product or component type
Counter module
Electrical connection
2 spring terminal blocks
Complementary
Number of modules
3 counter modules per TM238 base
Discrete input number
12 conforming to EN/IEC 61131-2 type 1
Discrete output number
4
Application specific I/O
Axis following
Downcounting
Frequency generator
Frequency meter
Period measurement
Upcounting
Counting mode
8 mode configurable
Counter inputs resolution
31 bits + sign
Counting frequency
60 kHz
Cycle time
1 ms
Input compatibility
2 and 3-wire sensors (24 V)
Incremental signal encoder with 15...30 V source outputs
Type of cable
Shielded cable , counting frequency: >= 1 kHz
Isolation between channels and internal logic
1500 V for 1 minute
Discrete input type
IN_A high-speed
IN_B high-speed
IN_CAP auxiliary input
IN_EN auxiliary input
IN_REF auxiliary input
IN_SYNC high-speed
Discrete input logic
Positive logic (sink)
Discrete input voltage
24 V DC
Voltage state 1 guaranteed
15...30 V
Current state 1 guaranteed
5 mA
Voltage state 0 guaranteed
<= 5 V
Current state 0 guaranteed
<= 0.5 mA
Discrete input current
>= 2 mA at 11 V
Discrete output logic
Positive logic (source)
Discrete output voltage
24 V DC (limits: 19.2...30 V)
Discrete output current
0.5 A
Load current
0.5 A per output
2 A per module
Response time on output
<= 200 µs on energisation/de-energisation
Leakage current
<= 0.1 mA at state 0
Voltage drop
<= 3 V at state 1
Output short-circuit current
> 0.5...1.5 A per output
Short-circuit protection
Automatic reset after disappearance of fault
Output overload protection
Automatic reset after disappearance of fault
Fallback status
Each channel held at its last value or set to the predefined value (0 or 1)
Faulty channel set to 0
Load inductance
L = 0.5/I²F
Load capacitance
50 µF
Local signalling
1 display block
Current consumption
<= 100 mA 24 V DC (internal supply)
<= 100 mA 5 V DC (internal supply)
<= 2 A 24 V DC (external power supply)
Mounting support
35 mm symmetrical DIN rail