No comment |
>
Control System >
PLC >
Delta PLC >
PLC 4 AI Analog Module DVP04AD-SL Delta NewDVP04AD-SL Delta PLC 4 group 16-bit resolution Analog I/O Module Original brand new
Introduction
The analog input module of DVP04AD-SL series can read/write the data of analog input module by using instructions FROM/TO via DVP SV/EH2-L MPU program. The analog input module receives 16bit digital data of 4 groups from PLC MPU and converts it into 4 points analog input signal either in voltage or in current. Users can select input from voltage or current via wiring. Voltage input range is -10V~10VDC (resolution is 312.5uV). Current input range is -20mA ~ 20mA (resolution is 625nA).
Electrical Specifications
Analog/Digital module
Voltage input
Current input
Power supply voltage
24VDC (-15% ~ +20%) / 3.5W
DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A)
Analog input channel
4 channels / each module
Range of analog input
+-10V
+-5V
+-20mA
0 ~ 20mA
4 ~ 20mA
Range of digital
conversion
+-32,000
+-32,000
+-32,000
0~32,000
0~32,000
Hardware Resolution
16 bits
16 bits
16 bits
15 bits
15 bits
Input impedance
< 0.5?
Overall accuracy
+-0.3% when in full scale (25°C, 77°F)
+-0.5% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F)
Response time
250us / each channel
Max. output current
1K? ~ 2M?
--
Tolerance carried
impedance
--
0?~500?
Digital data format
2’s complement of 16 bits, 15 significant bits
Isolation method
Optical coupler isolation between digital circuits and analog circuits.
No isolation among analog channels.
500VDC between digital circuits and Ground
500VDC between analog circuits and Ground
500VDC between analog circuits and digital circuits
500VDC between 24VDC and Ground
Series connection to DVP-PLC MPU
Connectable to the left side of MPU, numbered from 100 to 107 according to the position of module from the closest to farthest to MPU.
Operation/storage
temperature
Operation: 0°C~55°C (temp.), 50~95% (humidity), Pollution degree2
Storage: -25°C~70°C (temp.), 5~95% (humidity)
Vibration/shock
immunity
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/
IEC61131-2 & IEC 68-2-27 (TEST Ea)
Product Profile & Dimension
No comment |