No comment |
>
Control System >
PLC >
Delta PLC >
DTE10T Delta Temperature Controller main unit Input 24VDC 4-channel TC RS-485 NewDTE10T Delta Temperature Controller main unit Input 24VDC 4-channel TC RS-485 NewDelta Temperature Controller (TC) DTE Series:
Features
DTE series is a multi-channel modular temperature controller, supporting maximum 8 groups of thermocouple/platinum resistance input. The DIN rail installation saves wires, and the controller on each channel can work independently at the same time. DTE offers several output modules (relay, voltage pulse, current output and linear voltage output). The built-in 2-wire RS-485 communication is able to reach baud rate of 115,200bps. In programmable control, DTE is able to set up 64 sets of different temperature and control time. In addition, maximum 7 DTC2000 controllers are extendable to DTE, and DTE supports the synchronous communication protocol and auto ID setup function which DTC series also supports.
Specifications
PID, ON/OFF, programmable PID or manual control are available.
PID auto-tuning
Programmable control for 8 patterns and 8 steps in each pattern
12 modes ready for alarm output
°C or °F for the temperature unit
?Built-in RS-485 communication interface which supports Modbus ASCII/RTU and baud rate of up to 115,200bps.
Extendable to maximum 7 DTC2000 digital controllers
Supports synchronous communication protocol and auto ID setup function.
Supports various selections of input/output modules, e.g. relay output, voltage pulse output, current output, analog voltage output, parameter display and setup.
Supports CT functions, over-current and off-line alarm
Applications
Airconditioning system, plastic machinery
Specifications
Power input
24 VDC, isolated switching power supply
Voltage range
90 to 110% rated voltage
Power consumption
Max. 10W + 3W × number of DTC2000 controllers connected in parallel (Max. 7)
Input sensor
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Platinum resistance: Pt100, JPt100, Cu50
Sampling cycle
Thermocouple or platinum resistance: 1.0 second/all input
Control method
PID, PID programmable, manual, ON/OFF
Output accessories
(optional)
Relay output: SPST, Max. 250 VAC load, 3 A resistive load
Voltage pulse output: 12 VDC, Max. 40 mA current output
Current output: DC 4 to 20 mA output (resistive load < 500?); for OUT1 and OUT2 only
Analog voltage output: 0 to 10 V (resistive load > 1,000?); for OUT1 and OUT2 only
Output functions
Control output, alarm output or proportional output (proportional output is only applicable in the model with
linear voltage and current output for OUT1, OUT2)
Alarm modes
13 alarm modes available
Communication
RS-485 digital communication; supports baudrate 2,400 to 115,200 bps
Communication protocol
Supports Modbus ASCII/RTU
Extension port
The extension port transmits 24V power supply and communication signals to extension module DTC2000.
Vibration resistance
10 ~ 55Hz 10m/s 2 3 axes 10mins
Shock resistance
Max. 300m/s 2 3 axes 6 directions, 3 times each
Ambient temperature
0 to +50°C
Storage temperature
-20 to +65°C
Operation altitude
< 2,000m
Ambient humidity
35 to 85% RH (non-condensing)
Pollution degree
2
No comment |