No comment |
TM200HSC206DT Schneider PLC ModuleIf you need more than 10pcs and want to get better wholesale price, please feel free to contact us by following:
email:[email protected]
Tel:0086-574-88333153
We will quote you our best price to you in 24hours.Schneider PLC Module TM200HSC206DT
Product description:
Number of modules 3 counter modules per TM238 base
Discrete input number 12 conforming to EN/IEC 61131-2 type 1
Discrete output number 4
Application specific I/O Axis following
Downcounting
Frequency generator
Frequency meter
Period measurement
Upcounting
Counting mode 8 mode configurable
Counter inputs resolution 31 bits + sign
Counting frequency 60 kHz
Cycle time 1 ms
Input compatibility 2 and 3-wire sensors (24 V)
Incremental signal encoder with 15...30 V source outputs
Type of cable Shielded cable , counting frequency: ≥ 1 kHz
Isolation between channels and internal logic 1500 V for 1 minute
Discrete input type IN_A high-speed
IN_B high-speed
IN_CAP auxiliary input
IN_EN auxiliary input
IN_REF auxiliary input
IN_SYNC high-speed
Discrete input logic Positive logic (sink)
Discrete input voltage 24 V DC
Voltage state 1 guaranteed 15...30 V
Current state 1 guaranteed 5 mA
Voltage state 0 guaranteed ≤ 5 V
Current state 0 guaranteed ≤ 0.5 mA
Discrete input current ≥ 2 mA at 11 V
Discrete output logic Positive logic (source)
Discrete output voltage 24 V DC (limits: 19.2...30 V)
Discrete output current 0.5 A
Load current 0.5 A per output
2 A per module
Response time on output ≤ 200 µs on energisation/de-energisation
Leakage current ≤ 0.1 mA at state 0
Voltage drop ≤ 3 V at state 1
Output short-circuit current > 0.5...1.5 A per output
Short-circuit protection Automatic reset after disappearance of fault
Output overload protection Automatic reset after disappearance of fault
Fallback status Each channel held at its last value or set to the predefined value (0 or 1)
Faulty channel set to 0
Load inductance L = 0.5/I²F
Load capacitance 50 µF
Local signalling 1 display block
Current consumption ≤ 100 mA 24 V DC (internal supply)
≤ 100 mA 5 V DC (internal supply)
≤ 2 A 24 V DC (external power supply)
Benefits?
Flexible configuration, compact struction, stong function, fluent communication method,updatable firmware.
Applications?
Simple stand-alone installations: lighting management, heating and air conditioning, access control, control/monitoring...
Repetitive and comFlexible configuration,compact struction,stong function,fluent communication method,updatable firmware
pact machines: conveyers, lifts, automatic dispensers..
No comment |