No comment |
TM2AMI2LT
Main
Range of product | Modicon M238 logic controller |
Product or component type | Analog input module |
Analogue input number | 2 |
Analogue input type | Thermocouple - 200...760 °C thermocouple J , differential |
Cross talk | <= 2 LSB |
Complementary
Range compatibility | Advantys OTB |
Input level | Low level |
Analogue input resolution | 12 bits |
LSB value | 0.1 °C , thermocouple (thermocouple T) |
Permissible continuous overload | +/- 7.5 V , thermocouple |
Input impedance | ≥ 1 MOhm (thermocouple) |
Sampling duration | ≤ 200 ms |
Acquisition period | 200 ms per channel + 1 controller cycle time |
Measurement error | 0.2 % +/- 5 °C of full scale 25 °C |
Temperature coefficient | +/-0.006 %FS/°C |
Repeat accuracy | +/-0.5 %FS |
Non-linearity | +/- 0.2 %FS |
Total error | +/-1 %FS |
Type of cable | Shielded cable |
Insulation between channel and internal logic | Photocoupler |
Supply | External supply |
[Us] rated supply voltage | 24 V DC |
Supply voltage limits | 20,4...28,8 V |
Electrical connection | 1 removable screw terminal block |
Current consumption | 30 mA 24 V DC (external) |
Product weight | 0,085 kg |
Environment
Dielectric strength | 500 V between the I/O and the external supply circuit |
RoHS EUR conformity date | 0804 |
RoHS EUR status | Compliant |
TM2AMI2LT M238 PLC Module 2AI NewTM2AMI2LT
Main
Range of product
Modicon M238 logic controller
Product or component type
Analog input module
Analogue input number
2
Analogue input type
Thermocouple - 200...760 °C thermocouple J , differential
Thermocouple - 270...1370 °C thermocouple K , differential
Thermocouple - 270...400 °C thermocouple T , differentialCross talk
<= 2 LSB
Complementary
Range compatibility
Advantys OTB
TwidoInput level
Low level
Analogue input resolution
12 bits
LSB value
0.1 °C , thermocouple (thermocouple T)
0.325 °C , thermocouple (thermocouple K)
0.3 °C , thermocouple (thermocouple J)Permissible continuous overload
+/- 7.5 V , thermocouple
Input impedance
≥ 1 MOhm (thermocouple)
Sampling duration
≤ 200 ms
Acquisition period
200 ms per channel + 1 controller cycle time
Measurement error
0.2 % +/- 5 °C of full scale 25 °C
Temperature coefficient
+/-0.006 %FS/°C
Repeat accuracy
+/-0.5 %FS
Non-linearity
+/- 0.2 %FS
Total error
+/-1 %FS
Type of cable
Shielded cable
Insulation between channel and internal logic
Photocoupler
Supply
External supply
[Us] rated supply voltage
24 V DC
Supply voltage limits
20,4...28,8 V
Electrical connection
1 removable screw terminal block
Current consumption
30 mA 24 V DC (external)
60 mA 5 V DC (internal)Product weight
0,085 kg
Environment
Dielectric strength
500 V between the I/O and the external supply circuit
2500 V between the I/O and internal logicRoHS EUR conformity date
0804
RoHS EUR status
Compliant
No comment |