DVP32ES211T Delta PLC 240VAC 16DI 16DO relay output Standard Original brand newDVP32ES211T Delta PLC 240VAC 16DI 16DO relay output Standard Original brand new
Introduction
DVP-ES2 series provides 16~ 60 points MPU and 8 ~ 32 points digital I/O module. The maximum I/O points including those on the MPU are 256 points. DVP-ES2 can be used for various applications with different I/O points, power supply, digital I/O and analog I/O modules.
Specification
DVP32ES211T
Power supply
voltage
24VDC
(-15~+20%)
Connector
European standard removable terminal block (Pin pitch: 5mm)
Operation
DVP-ES2 starts to run when the power rises to 20.4VDC~28.8VDC and stops when the power drops to 17.5VDC. If the power is suddenly cut off, the MPU will continue running for 10ms.
Power supply
fuse
2.5A / 30VDC, Polyswitch
Power
consumption
1.8W
DC24V current
output
--
Power supply
protection
--
Voltage
withstand
1,500VAC (Primary-secondary), 1,500VAC (Primary-PE),
500VAC (Secondary-PE)
Insulation
resistance
> 5M ohm at 500VDC (between all I/O points and ground)
Noise immunity
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 1KV
RS: 26MHz ~ 1GHz, 10V/m
Grounding
The diameter of grounding wire shall not be less than that of L, N terminal of the power supply. (When many PLCs are in use at the same time, please make sure every PLC is properly grounded.)
Environment
Operation: 0°C~55°C (temperature), 50~95% (humidity), pollution degree 2
Storage: -25°C~70°C (temperature), 5~95% (humidity)
Agency
approvals
UL508 European community EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC
Vibration/shock
immunity
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)
Weight
T: 321g