No comment |
>
Control System >
Inverter >
22F-D2P5N103 Rockwell PowerFlex 4M 380V 0.75KW NEW22F-D2P5N103 Rockwell PowerFlex 4M 380V 0.75KW NEWIf you need more than 10pcs and want to get better wholesale price, please feel free to contact us by following:
email:[email protected]
Tel:0086-574-88333153
We will quote you our best price to you in 24hours.The High-end Inverter
Providing users with powerful motor speed control in a compact, space saving design, the Allen-Bradley® PowerFlex® 4M AC drive is the smallest and most cost effective member of the PowerFlex® family of drives. Ideal for machine level speed control, the PowerFlex 4M drive provides the application versatility to meet the demands ofglobal OEMs and end users who require space savings and easy-to-use AC drives that provide application flexibility, feed-through wiring and ease-of-programming. The PowerFlex 4M AC drive is available in three frame sizes (A, B and C) and power ratings from 0.2 to 11 kW (0.25 to 15 Hp) and in voltage classes of 120, 240 and 480 volts.What can you expect from Mitsubishi FR-A700?
Environmental Specifications
Category
Specification
Altitude:
1000 m (3300 ft) maximum without derating
Maximum Surrounding Air Temperature without Derating
IP20:
IP20 Zero Stacking:
-10…50 °C (14…122 °F)
-10…40 °C (14…104 °F)Cooling Method
Convection:
Fan:
120V, Single-Phase, 0.75 kW (1 HP) and below
240V, Single-Phase, 0.4 kW (0.5 HP) and below
240V, Three-Phase, 0.75 kW (1 HP) and below
480V, Three-Phase, 0.75 kW (1 HP) and below
All other drive ratings.Storage Temperature:
-40…85 °C (-40…185 °F)
Atmosphere:
Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Relative Humidity:
0 to 95% non-condensing
Shock:
15 g peak for 11 ms duration (±1.0 ms)
Vibration:
1 g peak, 5 to 2000 Hz
Technical SpecificationsCategory
Specification
Protection
Motor Protection:
I2t overload protection - 150% for 60 seconds, 200% for 3 seconds (provides Class 10 protection)
Overcurrent:
200% hardware limit, 300% instantaneous fault
AC Input Overvoltage Trip
100…120V:
200…240V:
380…460V:
150V AC
290V AC
575V ACAC Input Undervoltage Trip
100…120V:
200…240V:
380…460V:
75V AC
150V AC
275V ACBus Overvoltage Trip
100…120V:
200…240V:
380…460V:
405V DC
405V DC
810V DCBus Undervoltage Trip
100…120V:
200…240V:
380…460V:
210V DC
210V DC
390V DCLogic Control Ride-Thru:
Minimum is 0.5…2 seconds, typical
Faultless Power Ride-Thru:
100 milliseconds
Dynamic Braking:
Internal brake IGBT included with power ratings 5.5 kW (7.5 HP) and 7.5 kW (10.0 HP) for 240V, 3-phase drives and 5.5 kW (7.5 HP), 7.5 kW (10.0 HP) and 11.0 kW (15.0 HP) for 480V, three-phase drives.
Recommended Fuses/Circuit Breakers
Fuse:
Circuit Breakers:
UL Class J, RK1, T or Type BS88; 600V (550V) or equivalent.
HMCP or Bulletin 140M or equivalent.Electrical
Efficiency:
97.5% (Typical)
Voltage Tolerance:
200…240V, 380…480V, 460…600V: ±10%
Input Frequency Tolerance:
48…63 Hz
Input Phases:
Three-phase input provides full rating. Single-phase operation provides 35% rated current.
Displacement Power Factor:
0.98 across entire speed range
Maximum Short Circuit Rating:
100,000 Amps symmetrical
Actual Short Circuit Rating:
Determined by AIC Rating of installed fuse/circuit breaker.
Transistor Type:
Isolated Gate Bipolar (IGBT)
Control
Carrier Frequency:
2…10 kHz. Drive rating based on 4 kHz.
Output Frequency:
0…400 Hz (Programmable)
Frequency Accuracy
Digital Input:
Analog Input:
Within ±0.05% of set output frequency.
Within 0.5% of maximum output frequency.Speed Regulation - Open Loop with Slip Compensation:
±2% of base speed across a 40:1 speed range.
Stop Modes:
Multiple programmable stop modes including; Ramp, Coast, DC Brake, Ramp-to-Hold and S Curve.
Accel/Decel:
Two independently programmable accel and decel times. Each time may be programmed from 0…600 seconds in 0.1 second increments.
Intermittent Overload:
150% Overload capability for up to 1 minute
200% Overload capability for up to 3 secondsElectronic Motor Overload Protection:
Class 10 protection with speed sensitive response and power-down overload retention function.
Control I/O
Digital Control Inputs
Current:
SRC (Source) Mode:
SNK (Sink) Mode:
6 mA
On = 18…24V, Off = 0…6V
On = 0…6V, Off = 18…24VAnalog Control Inputs
0…10V DC:
4…20 mA:
External Pot:
100k ohm input impedance
250 ohm input impedance
1…10k ohms, 2 Watt minimumControl Output
Resistive Rating:
Inductive Rating:Programmable Output, Form C Relay
3.0 A at 30V DC, 125 and 240V AC
0.5 A at 30V DC, 125 and 240V AC