No comment |
VM05-22K Sanken Inverter SRMCO-VM05 series NEWIf you need more than 10pcs and want to get better wholesale price, please feel free to contact us by following:
email:[email protected]
Tel:0086-574-88333153
We will quote you our best price to you in 24hours.VM05-2.2K Sanken Inverter SRMCO-VM05 series
The High-end Inverter
Overview:
The SAMCO-vm05 Series of general-purpose inverters boasts revolutionary performance born from Sanken's superlative technological capabilities.
To meet diversified needs, the SAMCO-vm05 Series offers a powerful array of features, including dual-rated specifications selectable to best suit the intended application, the industry's first software customization function, and control algorithms provided as standard.
Dual-rated specifications for cost reduction
Two types of rated specifications - H characteristic and P characteristic can be selected according to the load status, for a wider range of standard applicable motors and substantial cost reduction (200 V type STB Series).
Industry's first software customize function
Dedicated functions can be created by adding various types of software, according to the customer's requirements. Users can also perform program changes and upgrades following purchase.
Control algorithms for various types of applications provided as standard
Control algorithms for diverse applications, such as winding control, multiple pump drive control and fixed-time inching, are provided as standard. This can be used as a dedicated inverter to meet diversified system needs.
Operability and communication functions developed with ease of use
The RS-232C interface, allowing direct connection to personal computers, and the RS-485 interface, effective in operation management in a system, are provided as standard.
Expandability with PG feedback
Vector control operation is realized through a PG feedback board (option).
Specifications:
Model
SBT-
0.75K
/1.5KSBT-
1.5K
/2.2KSBT-
2.2K
/3.7KSBT-
3.7K
/5.5KSBT-
5.5K
/7.5KSBT-
7.5K
/11KSBT-
11K
/15KSBT-
15K
/18.5KSBT-
18.5K
/22KSBT-
22K
/30K
H
P
H
P
H
P
H
P
H
P
H
P
H
P
H
P
H
P
H
P
0.75
1.5
1.5
2.2
2.2
3.7
3.7
5.5
5.5
7.5
7.5
11
11
15
15
18.5
18.5
22
22
30
1.9
2.7
3.0
3.7
4.3
5.8
6.7
8.5
9.1
11.4
12.8
16.8
17.5
21.7
22.9
25.9
28.6
31.2
33.5
41.9
5.1
7.0
8.0
9.6
11.2
15.1
17.6
22.3
24
30
33
44
46
57
60
68
75
82
88
110
Output
Load*1
8.4
12.0
11.5
16.8
18.1
26.4
26.7
36
36
49.5
52.8
69
68.4
90
81.6
112.5
98.4
132
132
Input
Applicable
motor
capacity
[kW]200V 50/60Hz 220V 60Hz
Rated
capacity
[kVA]*23φ 200V to 230V 50/60Hz
Rated
current
[A]Voltage: ±10%,
frequency: ±5%, voltage imbalance: 3% max.
Overload
current
[A]*31% or more (Use the optional reactor if less than 1%)
Protective
structureShutdown method (IP20)
Cooling
methodSelf-cooling
Forced air cooling
Gross
weight3kg
4kg
4kg
4.5kg
8kg
8kg
10kg
12kg
15kg
18kg
Control
functionsControl
methodV/f control or sensorless vector control
High-frequency
carrierSine wave PWM (carrier frequency: 1 to 14 kHz)*4
Output
frequency
rangeH
0.05 to 600 Hz (starting frequency: 0.05 to 20 Hz, variable)*5
P
0.01Hz (0.05 to 600Hz)
Frequency
setting
resolutionDigital
setting0.01 Hz (0.05 to 600 Hz)
Analog
setting0.1% (10 bits for 0 to 10 V, 4 to 20 mA), 0.2% (9 bits for 0 to 5 V) for maximum output frequency
Frequency
accuracyDigital
setting±0.01% of output frequency (at 10 to 40°C)
Analog
setting±0.2% of maximum output frequency (at 25°C ±10°C)*6
DC braking
Starting frequency (0.2 to 20 Hz), operation time (0.1 to 10 s), braking force (1 to 10 steps)
Additional
functionsRestart after momentary power failure, scooping-up start, multi-speed operation, frequency jump, auto alarm recovery,
PID control operation, simple scheduled operation, energy-saving operation, torque limiter (for sensorless vector control only)Operational
functionsStart/
stop settingOperation panel, serial communication (RS485, RS232C), control circuit terminals
Frequency
command
settingDigital
settingOperation panel, serial communication (RS485, RS232C), step setting from terminal board
Analog
setting2 external channels: 0 to 5 V, 0 to 10 V, 4 to 20 mA, external variable resistor (5 kΩ , 0.3 W or higher)
Input signals
Frequency command, forward run command, reverse run command, acceleration/
deceleration time setting, free-run stop/
alarm reset, emergency stop, jogging selection, step frequency setting, operation signal hold, torque limiter (sensorless vector control only),
(Digital input: 8 channels (arbitrary allocation available)) (Analog input: 1 channel for current and voltage)
Contact
outputAlarm batch and multifunctional contact output (1C contact, 250 VAC, 0.3 A)
Monitor
signalsOperating, frequency matching, overload alarm, undervoltage, frequency approach
(Open-collector output: 3 channels (arbitrary allocation available), Analog output: 2 channels)Output
signalsFrequency, output current, number of synchronous rotations, load factor, output voltage, pressure, line speed (no units), operating, alarm
Serial
communication
I/FRS485, RS232C
Function
extensionSoftware upgrade via RS232C serial communication supported
External power
supply output24 VDC, 150 mA (control terminal board)
Protection
functionsCurrent limiting, overcurrent shutoff, motor overload, external temperature,
undervoltage, overvoltage, momentary power failure, fin overheat, open phaseWarning
functionsOvervoltage prevention, current limiting during acceleration/deceleration, brake resistor overheat, overload, overheating of radiator fins
Environment
Ambient
temperatureH
-10 to +50°C (Top ventilation cover to be removed at +40°C and higher)
P
10 to +40°C (Top ventilation cover to be removed at +30°C and higher for SBT-3.7K/5.5K and earlier models)
Storage
temperature-20 to +65°C*7
Relative
humidity90% or less (with no condensation)
Operating
environmentIndoors at 1,000 m or lower altitude (No direct sunlight,
corrosive or inflammable gases, oil mist, or dust)1 H: H characteristic - Constant torque load (for general industry),
P: P characteristic - Dual law decreasing torque load (for fans and pumps)2 Rated capacity at an output voltage of 220 V
3 1 minute every 10 minutes
4 The maximum carrier frequency varies depending on the rated characteristics and the operating status.
5 The frequency setting range for sensorless vector control is 1 to 130 Hz for a four-pole motor (depends on the number of poles).
6 The maximum output frequency is at 5 V, 10 V, and 20 mA.
7 This temperature is for short periods, such as during transportation.
The SBT-7.5K/11K and earlier models are equipped with discharge resistors as stanuipped with discharge resistors as standard.
No comment |