No comment |
22A-A3P6N113 Rockwell PowerFlex 4 220V 0.75KW NEWIf you need more than 10pcs and want to get better wholesale price, please feel free to contact us by following:
email:[email protected]
Tel:0086-574-88333153
We will quote you our best price to you in 24hours.22A-A3P6N113 Rockwell PowerFlex 4 220V 0.75KW NEW
The High-end Inverter
Designed to meet global OEM and end-user demands for simplicity, space savings, and cost efficiency, this drive provides intuitive features such as an integral keypad with local potentiometer and control keys that are active right out of the box.
Technical Specifications
Category
Specification
Protection
Motor Protection:
I2t overload protection - 150% for 60 seconds, 200% for 3 seconds (provides Class 10 protection)
Overcurrent:
200% hardware limit, 300% instantaneous fault
AC Input Overvoltage Trip
100…120V:
200…240V:
380…480V:
150V AC
290V AC
575V ACAC Input Undervoltage Trip
100…120V:
200…240V:
380…480V:
75V AC
150V AC
275V ACBus Overvoltage Trip
100…120V:
200…240V:
380…480V:
405V DC
405V DC
810V DCBus Undervoltage Trip
100…120V:
200…240V:
380…480V:
210V DC
210V DC
390V DCLogic Control Ride-Thru:
Minimum is 0.5 seconds - 2 seconds, typical
Faultless Power Ride-Thru:
100 milliseconds
Dynamic Braking
Internal brake IGBT included with all ratings except No Brake versions.
Recommended Fuses/Circuit Breakers
Fuse:
Circuit Breakers:
UL Class J, CC, T or Type BS88; 600V (550V) or equivalent.
HMCP circuit breaker or equivalent.Electrical
Efficiency:
97.5% (Typical)
Voltage Tolerance:
120V, 200…240V, 380…480V, 460…600V: ±10%
Frequency Tolerance:
48…63 Hz
Displacement Power Factor:
0.98 across entire speed range
Maximum Short Circuit Rating:
100,000 Amps symmetrical
Control
Carrier Frequency:
2…16 kHz. Drive rating based on 4 kHz.
Output Frequency:
0…240 Hz (Programmable)
Frequency Accuracy
Digital Input:
Analog Input:
Within ±0.05% of set output frequency.
Within 0.5% of maximum output frequency.Speed Regulation - Open Loop with Slip Compensation:
±2% of base speed across a 40:1 speed range.
Stop Modes:
Multiple programmable stop modes including; Ramp, Coast, DC Brake, Ramp-to-Hold and S Curve.
Accel/Decel:
Two independently programmable accel and decel times. Each time may be programmed from 0…600 seconds in 0.1 second increments.
Intermittent Overload:
150% Overload capability for up to 1 minute
200% Overload capability for up to 3 secondsElectronic Motor Overload Protection:
Class 10 protection with speed sensitive response.
Control I/O
Digital Control Inputs
Current:
SRC (Source) Mode:
SNK (Sink) Mode:
6 mA
On = 18…24V, Off = 0…6V
On = 0…6V, Off = 18…24VAnalog Control Inputs
0…10V DC:
4…20 mA:
External Pot:
100k ohm input impedance
250 ohm input impedance
1…10k ohms, 2 Watt minimumControl Output
Resistive Rating:
Inductive Rating:Programmable Output, Form C Relay
3.0 A at 30V DC, 125 and 240V AC
0.5 A at 30V DC, 125 and 240V AC
No comment |