No comment |
>
Control System >
Inverter >
ATV303H037N4 VFD Inverter Input 3ph 380V Output 3ph 380~460V 1.5A 0.5~400Hz 0.37KW NewATV303H037N4 VFD Inverter Input 3ph 380V Output 3ph 380~460V 1.5A 0.5~400Hz 0.37KW NewATV303H037N4
ATV303 - From 0.37 to 11kW standard drive
Benefits
Design for China, best for China
A drive specially designed for China, the best solution for your application with the most easy way to use
High cost-effiective
Resistant to harsh environments
User-friendly programming and menu
Drive ratings
Three-phase supply voltage: 380V-460V 50/60 Hz
For three Phase Output 380V-460V motors
Motor
Line supply (input)
Drive (output)
Reference
Power
indicated
on plate (1)
Max. current line(2)
Apparent
power
Power
dissipated
at nominal
current
Nominal
current
Max.
transient
current for
At 380 V
At 460 V
60s
2s
kW
A
A
kVA
W
A
A
A
0.37
2.1
1.8
1.4
19.6
1.5
2.3
3.0
ATV303H037N4
0.75
3.5
3.1
2.5
28.8
2.3
3.5
4.6
ATV303H075N4
1.5
6.5
5.4
4.3
51.0
4.1
6.2
8.2
ATV303HU15N4
2.2
8.8
7.2
5.7
65.5
5.5
8.3
11.0
ATV303HU22N4
3
11.1
9.2
7.3
80.2
7.1
10.7
14.2
ATV303HU30N4
4
13.7
11.4
9.1
102.7
9.5
14.3
19.0
ATV303HU40N4
5.5
21.3
14.3
11.4
141.5
12.6
18.9
25.2
ATV303HU55N4
7.5
26.6
22.4
17.8
203.9
17
25.5
34.0
ATV303HU75N4
11
36.1
30.4
24.2
294.7
24
36.0
48.0
ATV303HD11N4
(1)These power ratings are for a Switching frequency range of 4 kHz, in continuous operation. The Switching frequency range is adjustable from 2 to 12 kHz.
Above 4 kHz, the drive will reduce the Switching frequency range if an excessive temperature rise occurs. Derating should be applied to the nominal drive current if continuous operation above 4 kHz is required:
10% derating for 8 kHz
20% derating for 12 kHz
(2)Line current network requirements:
* y 4kW, network short circuit current Isc y 5kA
* > 4kW, network short circuit current Isc y 22kA
Applications
Textile machines
Ceramic machines
Wood-working machines
Machine tools
Packaging & printing machines
Material handling, etc
Dimensions and weights
No comment |