No comment |
TM2AMI8HT M238 PLC Module 8AI New
TM2AMI8HT
Main
Range of product | Modicon M238 logic controller |
Product or component type | Analog input module |
Analogue input number | 8 |
Analogue input type | Current 4...20 mA , non differential |
Cross talk | <= 1 LSB |
Complementary
Range compatibility | Advantys OTB |
Analogue input resolution | 10 bits |
LSB value | 9.7 mV , voltage |
Permissible continuous overload | 13 V , voltage |
Input impedance | 470 Ohm (current) |
Sampling duration | ≤ 160 ms |
Acquisition period | 160 ms per channel + 1 controller cycle time |
Measurement error | +/- 0.2 % of full scale 25 °C |
Temperature coefficient | +/-0.01 %FS/°C |
Repeat accuracy | +/- 0.4 %FS |
Non-linearity | +/- 0.002 %FS |
Total error | +/-1 %FS |
Type of cable | Shielded cable |
Insulation between channel and internal logic | Photocoupler |
Supply | External supply |
[Us] rated supply voltage | 24 V DC |
Supply voltage limits | 20,4...28,8 V |
Electrical connection | 1 removable screw terminal block power supply |
Current consumption | 45 mA 24 V DC (external) |
Product weight | 0,085 kg |
Environment
Dielectric strength | 2500 V between the I/O and internal logic |
RoHS EUR conformity date | 0840 |
RoHS EUR status | Compliant |
TM2AMI8HT M238 PLC Module 8AI New
TM2AMI8HT
Main
Range of product
Modicon M238 logic controller
Product or component type
Analog input module
Analogue input number
8
Analogue input type
Current 4...20 mA , non differential
Voltage 0...10 V , non differentialCross talk
<= 1 LSB
Complementary
Range compatibility
Advantys OTB
TwidoAnalogue input resolution
10 bits
LSB value
9.7 mV , voltage
19.5 µA , currentPermissible continuous overload
13 V , voltage
40 mA , currentInput impedance
470 Ohm (current)
≥ 10 kOhm (voltage)Sampling duration
≤ 160 ms
Acquisition period
160 ms per channel + 1 controller cycle time
Measurement error
+/- 0.2 % of full scale 25 °C
Temperature coefficient
+/-0.01 %FS/°C
Repeat accuracy
+/- 0.4 %FS
Non-linearity
+/- 0.002 %FS
Total error
+/-1 %FS
Type of cable
Shielded cable
Insulation between channel and internal logic
Photocoupler
Supply
External supply
[Us] rated supply voltage
24 V DC
Supply voltage limits
20,4...28,8 V
Electrical connection
1 removable screw terminal block power supply
1 removable screw terminal block sensorsCurrent consumption
45 mA 24 V DC (external)
60 mA 5 V DC (internal)Product weight
0,085 kg
Environment
Dielectric strength
2500 V between the I/O and internal logic
RoHS EUR conformity date
0840
RoHS EUR status
Compliant
No comment |