TM2AMO2HTN M238 PLC Module 2AO NewTM2AMO2HTN
Specification
Voltage Output
Current Output
Input range
-10... +10 Vdc/0...10 Vdc
0...20 mA/4...20 mA
Input impedance
> 2 kohm
< 300ohm
Connectable I/O terminals
Removable terminal
Analog Outputs
2AO
Application load type
Resistive load
Setting time
10 ms
Total input system transfer time
10 ms + 1 scan time
Digital resolution
12 bits, including sign
Temperature drift
±0.06% of the full scale/°C
Output ripple
± 50 mV
Cross talk
60 dB
Non-linearity
± 0.5% of full scale
Output value of LSB
6 mV
10 μΑ
Protection type
Photo coupler between input and internal circuit
Output protection
short circuit protection
open circuit detection
Output behavior if input power supply
turn off
Cable Length
3 m is in compliance with electromagnetic immunity.
NOTE: Maximum 30 m shielded cables are used.
Weight
0.25kg