140ACI03000 Schneider ANALOG INPUT Module New140ACI03000 Schneider ANALOG INPUT Module NewSchneider ANALOG INPUT MODULE 140ACI03000
Product Description:
The Quantum 140ACI03000 Analog Input Module provides (8) differential analog input channels. Each channel is individually configurable for a 1 ... 5 VDC or 4 … 20 mA signal.
This module has broken wire detection in current mode and under voltage in voltage mode.
A Quantum removable terminal strip allows for easy maintenance.
Quantum backplanes (ordered separately) come in 2, 3, 4, 6, 10, and 16 slot versions. Any Quantum module can be used in any slot. A Quantum power supply is required in each rack. The power supply provides logic power to all modules on the bus.
All Quantum I/O modules are optically isolated from the bus, ensuring safe and trouble-free operation. This isolation also allows modules to be hot swapped.
Optionally, you can insert mechanical keys between the I/O module and the terminal strip to ensure that the field wiring and the module type are properly matched. Key codes are unique for each module type. Key kits are shipped with each I/O module.
Features:
Specifications
Module Type
8 analog inputs, differential
Bus Current Required 240 mA
240 mA
Signal Type
1…5VDC, 4…20mA
Update Time (in ms)
5 ms for all channels
Input Surge Tolerance
+/-30VDC, +/-25mA
Input to Input Isolation
30 VDC maximum
Input to Bus Isolation
1000 VDC, 3000 Vpp, for 1 minute
Linearity
+/- 0.04%
Internal Fuses 2A slow-blow (not user replaceable)
2A slow-blow (not user replaceable)
External Fuses - Supply 500mA fast-blow recommended
500mA fast-blow recommended
Common Mode Rejection > -72 dB @ 60 Hz
Differential
Filtering Single pole low pass wi
> -72 dB @ 60 Hz
Input Type Differential
Single pole low pass with -3 dB cutoff @ 15 Hz, +/- 20%
Signal Type
1 to 5 VDC
4 to 20 mA
Input impedance
> 20 MΩ
250 ? +/− 0.03%
Absolute Maximum Input
50 VDC
25 mA
Error at 25 degrees C
0.05% typical, 0.1% max
Resolution
12 bits
Power Dissipation
2 W
IO Map
9 Input words
EMC Immunity
UL, CUL, CSA, CE, FM Class 1 Div 2
Weight
2.0 lb (1 kg) Maximum
Accuracy Drift with Temperature
0 to 60 degrees C
EMC Emissions
Concept™, ProWORX®, Unity™
Agency Approvals
0.0025% / degree C typical, 0.005% / degree C max
Storage Temperature
IEC1131 - Surge on aux power supply 500 V
Operating Temperature
EN50081-2 (limitation A)
Software Support
-25 to +80 degrees C
Relative Humidity
5 … 95% Non-condensing