No comment |
>
Transducer/Sensor >
Photoelectric Sensors >
Photoelectric Switch >
IM30-15N-N-ZW0 SICK Inductive Proximity sensor NEWIM30-15N-N-ZW0 SICK Inductive Proximity sensor NEWProduct Description:
Operating distance up to 15 mm
ATEX device category 1G and 2G
Output according to DIN EN 60947-5-6
Types M30
Benefits:
Unsurpassed explosion protection
Category 1G and 2G for zones 0 and 1
Output according to DIN EN 60947-5-6
Features:
Sensing range Sn: 15 mm
Installation in metal: Non-flush
Switching frequency: 200 Hz
Connection type: Cable, 2-wire, 2 m
Switching output: NAMUR
Output function: NC
Enclosure rating: IP 67 1)
Switching mode: NC
1) According to EN60529
Mechanics/electronics:
Design: cylindrical
Housing length: 41 mm
Supply voltage: 7.5 V DC ... 25 V DC 1)
Power consumption: ≤ 30 mA 2)
Hysteresis: 1 % ... 15 %
Temperature drift (of sr):: ± 10 %
EMC: Nach EN 60947-5-6
Cable material: PVC
Conductor cross-section: 0.5 mm2
Cable diameter: 5.4 mm
Housing material: Metal, Nickel-plated brass
Housing cap: Plastic, PBT
Ambient temperature, operation: -20 °C ... 70 °C
Shock/vibration stress: 30 g, 11 ms/10 ... 55 Hz, 1 mm
Max. tightening torque: 50 Nm
Thread size: M30 x 1.5
EC type approval certificate: PTB 03 ATEX 2037
Hazardous area category: 1G, 2G
Marking of the unit: II 1 G Ex ia IIB T6 Ta: -20 °C ... +55 °C, II 2 G Ex ia IIC T6 Ta: -20 °C ... +70 °C
Thread lenght: 25 mm
Power consumption, attenuated: ≤ 1 mA
Power consumption, unattenuated: ≥ 2.2 mA
Cable resistance: 50 Ω
Input voltage Ui max: 15 V 3)
Input power Pimax.: 120 mW 4)
Input current Ii max: 50 mA 5)
Internal capacitance Ci max.: 145 nF 6)
Internal inductance Li max.: 110 µH 7)
Nominal voltage: 8.2 V DC
1) 2) When used outside the hazardous area 3) 4) 5) 6) 7) For connection only to a separately certified, intrinsically safe electrical circuit