No comment |
>
Low Voltage >
Others Electrical >
DTE20T Delta 4 channels of thermocouple Output Model NewDTE20T Delta 4 channels of thermocouple Output Model New
DTE Series
1.Please hold the plastic terminal when installing DTE20T/20P to prevent electrostatic discharge (ESD).
2. Prevent dust or metallic debris from falling into the device and cause malfunction. DO NOTmodify or uninstall
DTE20T/20P without being permitted. DO NOTuse empty terminals.
3.When installing DTE20T/20P, please make sure the power of DTE main unit is switched off and insert DTE20T/20P into
the correct slot on DTE main unit.
4.Make sure you install DTE20T/20P correctly before switching on the power; otherwise serious damage may occur.
5.DO NOT touch the terminals or repair the device when the power is on; otherwise an electric shock may occur
Power consumption
Max. 0.5W
Input sensor
DTE20T (4 channels of thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
DTE20P (3 channels of platinum RTD): Pt100, JPt100, Ni120, Cu50
Sampling cycle
Thermocouple or platinum RTD: 1.0 second (all inputs)
Terminal connection
Can only be inserted into INBslot on DTE10T or DTE10P main unit
The sensor slot (INA/INB) only accepts the same input type. For example, if you select DTE20T as accessory, you can
only use it on DTE10T main unit. If you select DTE20P as accessory, you can only use it on DTE10P main unit.