Why buy from us?
We offer competitive prices and quality services!
Ask a Question About This Product
- Stock: In Stock
- Model: E5CS-R1PU-W
- Weight: 0.50kg
2. Shipping options include DHL, UPS, FedEx, and EMS.
3. Estimated delivery time for express shipping via DHL, UPS, FedEx, or EMS generally ranges from 3 to 10 business days, depending on the destination country.
4. Please verify your address thoroughly when placing your order.
5. Important for buyers: You are responsible for any tariffs on accessories. To potentially avoid these tariffs, you may choose EMS express shipping.
6. The shipping service is responsible for any accidents, delays, or other issues that may arise.
Returns:
We offer a 14-day return policy. If you wish to return an item, please contact us within 14 days and ensure that the package remains unopened. The buyer is responsible for the shipping costs for both the return and the initial delivery, as well as any applicable customs fees. Once we receive and inspect the product, we will process your refund within 24 hours.
For any quality issues that arise during normal use within the warranty period, we will repair the item free of charge. The buyer is responsible for the return shipping cost, while our company will cover the cost of re-shipping the repaired item.
OMRON Thermostat E5CS-R1PU-W
Product Description:
Easy setting using DIP switch.
Models with two alarms added to Series, ideal for applications requiring alarms.
Universal-input (thermocouple/platinum resistance thermometer) models also available.
Clearly visible digital display with character height of 13.5 mm.
RoHS compliant.
Specifications:
Setting accuracy | Thermocouple *1: (±1% of indication value or ±2°C, whichever is greater) ±1 digit max. | |
Platinum resistance thermometer *2: (±0.5% of indication value or ±1°C, whichever is greater) ±1 | ||
digit max. | ||
Indication accuracy | Thermistor *3: (1% FS of indication value) ±1 digit max. | |
(ambient temperature of 23°C) |
| |
Influence of temperature | R thermocouple inputs: (±2% of PV or ±10°C, whichever is greater) ±1 digit max. | |
Other thermocouple inputs: (±2% of PV or ±4°C, whichever is greater) ±1 digit max. | ||
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. | ||
Influence of voltage | Thermistor: (±2% FS) ±1 digit max. | |
Hysteresis (for ON/OFF | 0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models) | |
control) | ||
Proportional band (P) | 1 to 999°C (automatic adjustment using auto-tuning/self-tuning) | |
Integral time (I) | 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning) | |
Derivative time (D) | 1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning) | |
Alarm output range | Absolute-value alarm: Same as the control range | |
Other: 0 to input setting range full scale (°C or °F) | ||
Alarm hysteresis: 0.2°C or °F (fixed) | ||
Control period | 2/20 s | |
Sampling period | 500 ms | |
Insulation resistance | 20 MΩ min. (at 500 VDC) | |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity | |
Vibration | Malfunction | 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions |
resistance | Destruction | 10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions |
Shock | Malfunction | 100 m/s2 min., 3 times each in six directions |
resistance | Destruction | 300 m/s2 min., 3 times each in six directions |
Life expectancy | Electrical | 100,000 operations min. (relay output models) |
Weight | Approx. 110 g (Controller only) | |
Degree of protection | Front panel: Equivalent to IP50, Enclosure Category 2 (IEC 60529), Rear case: IP20; Terminals: IP00 | |
Memory protection | EEPROM (non-volatile memory) (number of writes: 1,000,000) | |
EMC | EMI Radiated: EN 55011 Group 1 Class A | |
EMI Conducted: EN 55011 Group 1 Class A | ||
Radiated Electromagnetic Field Immunity: EN 61000-4-2: 4 kV contact discharge (level 2), | ||
8 kV air discharge (level 3) | ||
RF-interference Immunity: EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3), | ||
10 V/m (900 MHz pulse modulated) | ||
Conducted Disturbance Immunity: EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2) | ||
Noise Immunity (First Transient Burst Noise): EN 61000-4-4 | ||
Burst Immunity: 2 kV power-line (level 3), 1 kV I/O signal-line (level 3) | ||
Surge Immunity: EN 61000-4-5: Power line: Normal mode 1 kV; Common mode 2 kV, | ||
Output line (relay output): Normal mode 1 kV; Common mode 2 kV | ||
Voltage Dip/Interrupting Immunity: EN 61000-4-11 0.5 cycle, 100% (rated voltage) | ||
Approved standards | UL 61010-1 (listing) | |
CSA C22.2 No.1010-1 | ||
Conformed standards | EN 61326, EN 61010-1, IEC 61010-1 | |
*1.The following exceptions apply to thermocouples.
U, L: ±2°C ±1 digit max.
R: ±3°C ±1 digit max. at 200°C or less
*2.The following exception applies to platinum resistance thermometers.
Input set values 1 for E5CS-U: 1% FS ±1 digit max.
*3.The following exceptions apply to thermistors.
When the unit setting is °C, temperature indication ranges exceeding the set temperature range ±10% FS may not be accurate.
When the unit setting is °F, the temperature range for the input setting numbers 4 and 9 (609 to 630°F) and temperature indication ranges exceeding the set temperature range −5% FS to +10% FS may not be accurate.