Product Description:
SIMATIC S7-300, CPU 314C-2DP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 96 KBYTE WORKING MEMORY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED.
Features:
General information
Hardware product version
01
Firmware version
V2.0.0
Engineering with
Programming package
STEP 7 V5.2 + SP1 or higher with HW update
Supply voltage
24 V DC
Yes
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Load voltage L+
Rated value (DC)
24 V
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Input current
Current consumption (rated value)
1000 mA
Current consumption (in no-load operation), typ.
150 mA
Inrush current, typ.
11 A
I²t
0.7 A²·s
from supply voltage L+, max.
1000 mA
Power losses
Power loss, typ.
14 W
Memory
Work memory
integrated
64 kbyte; For program and data
expandable
No
Load memory
pluggable (MMC)
Yes
pluggable (MMC), max.
8 Mbyte
Data management on MMC (after last programming), min.
10 a
Backup
present
Yes; Guaranteed by MMC (maintenance-free)
without battery
Yes; Program and data
CPU processing times
for bit operations, min.
0.1 µs
for bit operations, max.
0.2 µs
for word operations, min.
0.2 µs
for fixed point arithmetic, min.
2 µs
for floating point arithmetic, min.
3 µs
CPU-blocks
Number of blocks (total)
1024
DB
Number, max.
511; Number range: 1 to 511
Size, max.
16 kbyte
FB
Number, max.
512; Number range: 0 to 2047
Size, max.
16 kbyte
FC
Number, max.
512; Number range: 0 to 2047
Size, max.
16 kbyte
OB
Number, max.
see instruction list
Size, max.
16 kbyte
Number of free cycle OBs
1; OB 1
Number of time alarm OBs
1; OB 10
Number of delay alarm OBs
1; OB 20
Number of time interrupt OBs
1; OB 35
Number of process alarm OBs
1; OB 40
Number of startup OBs
1; OB 100
Number of asynchronous error OBs
1; OB 80
Number of synchronous error OBs
2; OB 121, 122
Nesting depth
per priority class
8
additional within an error OB
4
Counters, timers and their retentivity
S7 counter
Number
256
of which retentive without battery
adjustable
Yes
lower limit
0
upper limit
256
Counting range
lower limit
0
upper limit
999
IEC counter
present
Yes
Type
SFB
S7 times
Number
256
Retentivity
adjustable
Yes
lower limit
0
upper limit
256
preset
No retentivity
Time range
lower limit
10 ms
upper limit
9990 s
IEC timer
present
Yes
Type
SFB
Data areas and their retentivity
retentive data area, total
all
Flag
Number, max.
256 byte
Retentivity available
Yes; MB 0 to MB 255
Retentivity preset
MB 0 to MB 15
Number of clock memories
8
Data blocks
Number, max.
511
Size, max.
16 kbyte
Retentivity adjustable
No
Retentivity preset
Yes
Local data
per priority class, max.
510 byte
Address area
I/O address area
Inputs
1 kbyte
Outputs
1 kbyte
Process image
Inputs
128 byte
Outputs
128 byte
Default addresses of the integrated channels
Digital inputs
124,0 to 126,7
Digital outputs
124.0 to 125.7
Analog inputs
752 to 761
Analog outputs
752 to 755
Digital channels
Inputs
992
Outputs
992
Inputs, of which central
992
Outputs, of which central
992
Analog channels
Inputs
512
Outputs
124
Inputs, of which central
248
Outputs, of which central
248
Hardware configuration
Racks, max.
4
Modules per rack, max.
8; In rack 3 max. 7
Expansion devices, max.
3
Number of DP masters
integrated
1
via CP
4
Number of operable FMs and CPs (recommended)
FM
8
CP, point-to-point
8
CP, LAN
10
Time of day
Clock
Hardware clock (real-time clock)
Yes
battery-backed and synchronizable
Yes
Deviation per day, max.
10 s
Backup time
6 wk
Operating hours counter
Number
1
Number/Number range
0
Range of values
0 to 2^31 hours (when using SFC 101)
Granularity
1 hour
retentive
Yes
Clock synchronization
supported
Yes
to MPI, master
Yes
to MPI, slave
Yes
in AS, master
Yes
Digital inputs
Number/binary inputs
24
integrated channels (DI)
24
Input voltage
Rated value, DC
24 V
for signal "0"
-3 to +5 V
for signal "1"
15 to 30 V
Input current
for signal "1", typ.
8 mA
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable
Yes; 0.1 / 0.3 / 3 / 15 ms
for counter/technological functions
at "0" to "1", max.
8 µs
Cable length
Cable length, shielded, max.
1000 m; 100 m for technological functions
Cable length unshielded, max.
600 m
Digital outputs
Number/binary outputs
16
integrated channels (DO)
16
Functionality/short-circuit strength
Yes; Clocked electronically
Limitation of inductive shutdown voltage to
L+ (-48 V)
Output voltage
for signal "1", min.
L+ (-0.8 V)
Output current
for signal "1" permissible range for 0 to 40 °C, max.
500 mA
for signal "1" permissible range for 0 to 60 °C, max.
500 mA
for signal "1" minimum load current
5 mA
for signal "0" residual current, max.
0.5 mA
Switching frequency
with resistive load, max.
100 Hz
with inductive load, max.
0.5 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 40 °C, max.
8 A
up to 60 °C, max.
4 A
Cable length
Cable length, shielded, max.
1000 m
Cable length unshielded, max.
600 m
Analog inputs
Integrated channels (AI)
4+1
Number of analog inputs for voltage/current measurement
4
Number of analog inputs for resistance/resistance thermometer measurement
1
permissible input frequency for current input (destruction limit), max.
5 V; Permanent
permissible input current for voltage input (destruction limit), max.
0.5 mA; Permanent
Technical unit for temperature measurement adjustable
Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
Input ranges
Current
Yes
Resistance thermometer
Yes
Resistance
Yes
Input ranges (rated values), voltages
0 to +10 V
Yes
Input resistance (0 to 10 V)
100 kΩ
Input ranges (rated values), currents
0 to 20 mA
Yes
Input resistance (0 to 20 mA)
100 Ω
-20 to +20 mA
Yes
Input resistance (-20 to +20 mA)
100 Ω
4 to 20 mA
Yes
Input resistance (4 to 20 mA)
100 Ω
Input ranges (rated values), resistance thermometers
Pt 100
Yes
Input resistance (Pt 100)
10 MΩ
Input ranges (rated values), resistors
0 to 600 ohms
Yes
Input resistance (0 to 600 ohms)
10 MΩ
Cable length
Cable length, shielded, max.
100 m
Analog outputs
Integrated channels (AO)
2
Number of analog outputs
2
Output ranges, voltage
0 to 10 V
Yes
-10 to +10 V
Yes
Output ranges, current
0 to 20 mA
Yes
-20 to +20 mA
Yes
4 to 20 mA
Yes
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.
12 bit
Integration time, parameterizable
Yes; 2.5 / 16.6 / 20 ms
Conversion time (per channel)
1 ms
Encoder
Connectable encoders
2-wire sensor
Yes
Permissible quiescent current (2-wire sensor), max.
1.5 mA
Errors/accuracies
No comment |