6ES7314-6BG03-0AB0 SIEMENS CPU Module New

prevnext

6ES7314-6BG03-0AB0 SIEMENS CPU Module New
  • Market price: $ 4468.2
  • Shop price: $ 1354.0
  • Goods click count: 266
  • Total:
  • Quantity:
Add to cart collect
  

Description

6ES7314-6BG03-0AB0 SIEMENS CPU Module New

SIEMENS CPU Module 6ES7314-6BG03-0AB0

Product Description:

SIMATIC S7-300, CPU 314C-2 PTP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED INTERFACE RS485, INTEGRATED 24V DC POWER SUPPLY, 96 KBYTE WORKING MEMORY, FRONT CONNECTOR (2 X 40PIN) AND MICRO MEMORY CARD REQUIRED.

Features:

General information

Hardware product version

01

Firmware version

V2.6

Engineering with

Programming package

STEP 7 V5.3 SP2 or higher with HW update

Supply voltage

24 V DC

Yes

permissible range, lower limit (DC)

20.4 V

permissible range, upper limit (DC)

28.8 V

External protection for supply cables (recommendation)

Miniature circuit breaker, type C; min 2 A; miniature circuit breaker type B, min. 4 A

Load voltage L+

Rated value (DC)

24 V

permissible range, lower limit (DC)

20.4 V

permissible range, upper limit (DC)

28.8 V

Digital inputs

Load voltage L+

Rated value (DC)

24 V

Reverse polarity protection

Yes

Digital outputs

Load voltage L+

Rated value (DC)

24 V

Reverse polarity protection

No

Analog outputs

Load voltage L+

Rated value (DC)

24 V

Reverse polarity protection

Yes

Input current

Current consumption (rated value)

800 mA

Current consumption (in no-load operation), typ.

150 mA

Inrush current, typ.

11 A

I²t

0.7 A²·s

from supply voltage L+, max.

800 mA

Digital inputs

from load voltage L+ (without load), max.

70 mA

Digital outputs

from load voltage L+, max.

100 mA

Power losses

Power loss, typ.

14 W

Memory

Work memory

integrated

96 kbyte

expandable

No

Load memory

pluggable (MMC)

Yes

pluggable (MMC), max.

8 Mbyte

Data management on MMC (after last programming), min.

10 a

Backup

present

Yes; Guaranteed by MMC (maintenance-free)

without battery

Yes; Program and data

CPU processing times

for bit operations, min.

0.1 µs

for bit operations, max.

0.2 µs

for word operations, min.

0.2 µs

for fixed point arithmetic, min.

2 µs

for floating point arithmetic, min.

3 µs

CPU-blocks

Number of blocks (total)

1024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.

DB

Number, max.

511; Number range: 1 to 511

Size, max.

16 kbyte

FB

Number, max.

1024; Number range: 0 to 2047

Size, max.

16 kbyte

FC

Number, max.

1024; Number range: 0 to 2047

Size, max.

16 kbyte

OB

Size, max.

16 kbyte; see instruction list

Number of free cycle OBs

1; OB 1

Number of time alarm OBs

1; OB 10

Number of delay alarm OBs

1; OB 20

Number of time interrupt OBs

1; OB 35

Number of process alarm OBs

1; OB 40

Number of startup OBs

1; OB 100

Number of asynchronous error OBs

4; OB 80, 82, 85, 87

Number of synchronous error OBs

2; OB 121, 122

Nesting depth

per priority class

8

additional within an error OB

4

Counters, timers and their retentivity

S7 counter

Number

256

of which retentive without battery

adjustable

Yes

lower limit

0

upper limit

255

preset

8

Retentivity

adjustable

Yes

lower limit

0

upper limit

255

preset

8

Counting range

lower limit

0

upper limit

999

IEC counter

present

Yes

Type

SFB

Number

Unlimited (limited only by RAM capacity)

S7 times

Number

256

of which retentive without battery

adjustable

Yes

lower limit

0

upper limit

255

Retentivity

adjustable

Yes

lower limit

0

upper limit

255

preset

No retentivity

Time range

lower limit

10 ms

upper limit

9990 s

IEC timer

present

Yes

Type

SFB

Number

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

retentive data area, total

All, max. 64 KB

Flag

Number, max.

256 byte

Retentivity available

Yes; MB 0 to MB 255

Retentivity preset

MB 0 to MB 15

Number of clock memories

8; 1 memory byte

Data blocks

Number, max.

511; Number range: 1 to 511

Size, max.

16 kbyte

Retentivity adjustable

Yes; via non-retain property on DB

Retentivity preset

Yes

Local data

per priority class, max.

510 byte

Address area

I/O address area

Inputs

1 kbyte

Outputs

1 kbyte

of which, distributed

Inputs

none

Outputs

none

Process image

Inputs

128 byte

Outputs

128 byte

Default addresses of the integrated channels

Digital inputs

124,0 to 126,7

Digital outputs

124.0 to 125.7

Analog inputs

752 to 761

Analog outputs

752 to 755

Digital channels

Inputs

1016

Outputs

1008

Inputs, of which central

1016

Outputs, of which central

1008

Analog channels

Inputs

253

Outputs

250

Inputs, of which central

253

Outputs, of which central

250

Hardware configuration

Racks, max.

4

Modules per rack, max.

8; In rack 3 max. 7

Expansion devices, max.

3

Number of DP masters

integrated

none

via CP

4

Number of operable FMs and CPs (recommended)

FM

8

CP, point-to-point

8

CP, LAN

10

Time of day

Clock

Hardware clock (real-time clock)

Yes

battery-backed and synchronizable

Yes

Deviation per day, max.

10 s

Backup time

6 wk; At 40 °C ambient temperature

Operating hours counter

Number

1

Number/Number range

0

Range of values

0 to 2^31 hours (when using SFC 101)

Granularity

1 hour

retentive

Yes; Must be restarted at each restart

Clock synchronization

supported

Yes

to MPI, master

Yes

to MPI, slave

Yes

in AS, master

Yes

Digital inputs

Number/binary inputs

24

of which, inputs usable for technological functions

16

integrated channels (DI)

24

Input characteristic curve acc. to IEC 61131, Type 1

Yes

Number of simultaneously controllable inputs

horizontal installation

up to 40 °C, max.

24

up to 60 °C, max.

12

vertical installation

up to 40 °C, max.

12

Technological functions

shielded, max.

50 m

Unshielded, max.

not allowed

Standard DI

shielded, max.

1000 m

Unshielded, max.

600 m

Input voltage

Rated value, DC

24 V

for signal "0"

-3 to +5 V

for signal "1"

15 to 30 V

Input current

for signal "1", typ.

9 mA

Input delay (for rated value of input voltage)

for standard inputs

Parameterizable

Yes; 0.1 / 0.3 / 3 / 15 ms

Rated value

3 ms

for counter/technological functions

at "0" to "1", max.

8 µs

Cable length

Cable length, shielded, max.

1000 m; 50 m for technological functions

Cable length unshielded, max.

600 m; For technological functions: No

Digital outputs

Number/binary outputs

16

of which high-speed outputs

4

integrated channels (DO)

16

Functionality/short-circuit strength

Yes; Clocked electronically

Response threshold, typ.

1 A

Limitation of inductive shutdown voltage to

L+ (-48 V)

Lamp load, max.

5 W

Controlling a digital input

Yes

Load resistance range

lower limit

48 Ω

upper limit

4 kΩ

Output voltage

for signal "1", min.

L+ (-0.8 V)

Output current

for signal "1" rated value

500 mA

for signal "1" permissible range, min.

5 mA

for signal "1" permissible range, max.

0.6 A

for signal "1" minimum load current

5 mA

for signal "0" residual current, max.

0.5 mA

Parallel switching of 2 outputs

for increased power

No

for redundant control of a load

Yes

Switching frequency

with resistive load, max.

100 Hz

with inductive load, max.

0.5 Hz

  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: