Your Position: Home > Control System > PLC > Siemens PLC > 6ES7314-1AG14-0AB0 SIEMENS CPU Module New

  Categories

Control System
Motion Control System
LCD Screen Panel
Instrumentation
Low Voltage
Transducer/Sensor
  

Service



Email: [email protected]
Tel: 0086-574-88333153

View History

   

6ES7314-1AG14-0AB0 SIEMENS CPU Module New

prevnext

6ES7314-1AG14-0AB0 SIEMENS CPU Module New
  • Market price: $ 1788.6
  • Shop price: $ 542.0
  • Goods click count: 281
  • Total:
  • Quantity:
Add to cart collect
  

Description

6ES7314-1AG14-0AB0 SIEMENS CPU Module New

SIEMENS CPU Module 6ES7314-1AG14-0AB0

Product Description:

SIMATIC S7-300, CPU 314 CPU WITH MPI INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 128 KBYTE WORKING MEMORY, MICRO MEMORY CARD NECESSARY.

Features:

General information

Hardware product version

01

Firmware version

V2.0.0

Engineering with

Programming package

STEP 7 V5.1 SP4 or higher

Supply voltage

24 V DC

Yes

permissible range, lower limit (DC)

20.4 V

permissible range, upper limit (DC)

28.8 V

External protection for supply cables (recommendation)

2 A min.

Input current

Current consumption (in no-load operation), typ.

60 mA

Inrush current, typ.

2.5 A

I²t

0.5 A²·s

from supply voltage L+, max.

600 mA

Power losses

Power loss, typ.

2.5 W

Backup battery

Battery operation

 

Backup time, max.

1008 h; At 40 °C ambient temperature

Memory

Work memory

integrated

48 kbyte

expandable

No

Load memory

pluggable (MMC)

Yes

pluggable (MMC), max.

8 Mbyte

Data management on MMC (after last programming), min.

10 a

Backup

present

Yes; Guaranteed by MMC (maintenance-free)

CPU processing times

for bit operations, min.

0.1 µs

for bit operations, max.

0.2 µs

for word operations, min.

0.2 µs

for fixed point arithmetic, min.

2 µs

for floating point arithmetic, min.

3 µs

CPU-blocks

Number of blocks (total)

1024; (DBs, FCs, FBs OBs, SDBs); the maximum number of loadable blocks can be reduced by the MMC being used.

DB

Number, max.

511; DB 0 reserved

Size, max.

16 kbyte

FB

Number, max.

512; From FB 0 to FB 511

Size, max.

16 kbyte

FC

Number, max.

512; from FC 0 to FC 511

Size, max.

16 kbyte

OB

Number, max.

see instruction list

Size, max.

16 kbyte

Nesting depth

per priority class

8

additional within an error OB

4

Counters, timers and their retentivity

S7 counter

Number

256

of which retentive without battery

adjustable

Yes

preset

Z 0 to Z 7

Retentivity

adjustable

Yes

Counting range

adjustable

Yes

lower limit

0

upper limit

999

IEC counter

present

Yes

Type

SFB

Number

Unlimited (limited only by RAM capacity)

S7 times

Number

256

Retentivity

adjustable

Yes

preset

No retentivity

Time range

lower limit

10 ms

upper limit

9990 s

IEC timer

present

Yes

Type

SFB

Number

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

retentive data area, total

All (incl. memory bits, times, counters)

Flag

Number, max.

256 byte

Retentivity available

Yes; MB 0 to MB 255

Retentivity preset

MB 0 to MB 15

Number of clock memories

8; 1 memory byte

Data blocks

Number, max.

511; from DB1 to DB511

Size, max.

16 kbyte

Local data

per priority class, max.

510 byte

Address area

I/O address area

Inputs

1 kbyte

Outputs

1 kbyte

Process image

Inputs

128 byte

Outputs

128 byte

Digital channels

Inputs

1024

Outputs

1024

Inputs, of which central

1024

Outputs, of which central

1024

Analog channels

Inputs

256

Outputs

256

Inputs, of which central

256

Outputs, of which central

256

Hardware configuration

Racks, max.

4

Modules per rack, max.

8

Number of DP masters

integrated

0

via CP

4

Number of operable FMs and CPs (recommended)

FM

8

CP, point-to-point

8

CP, LAN

10

Time of day

Clock

Hardware clock (real-time clock)

Yes

battery-backed and synchronizable

Yes

Deviation per day, max.

10 s

Backup time

6 wk; At 40 °C ambient temperature

Operating hours counter

Number

1

Number/Number range

0

Range of values

0 to 2^31 hours (when using SFC 101)

Granularity

1 hour

retentive

Yes; Must be restarted at each restart

Clock synchronization

supported

Yes

to MPI, master

Yes

to MPI, slave

Yes

in AS, master

Yes

Analog inputs

Integrated channels (AI)

0

Analog outputs

Integrated channels (AO)

0

1st interface

Type of interface

Integrated RS 485 interface

Physics

RS 485

Isolated

No

Power supply to interface (15 to 30 V DC), max.

200 mA

Functionality

MPI

Yes

DP master

No

DP slave

No

Point-to-point connection

No

MPI

Number of connections

12

Services

PG/OP communication

Yes

Routing

No

Global data communication

Yes

S7 basic communication

Yes

S7 communication

Yes

S7 communication, as client

No; but via CP and loadable FB

S7 communication, as server

Yes

Transmission rate, max.

187.5 kbit/s

Communication functions

PG/OP communication

Yes

Global data communication

supported

Yes

Number of GD loops, max.

4

Number of GD packets, max.

4

Number of GD packets, transmitter, max.

4

Number of GD packets, receiver, max.

4

Size of GD packets, max.

22 byte

Size of GD packet (of which consistent), max.

22 byte

S7 basic communication

supported

Yes

User data per job, max.

76 byte

User data per job (of which consistent), max.

76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)

S7 communication

supported

Yes

as server

Yes

as client

Yes; Via CP and loadable FB

User data per job, max.

180 byte; With PUT/GET

User data per job (of which consistent), max.

64 byte

S5-compatible communication

supported

Yes; via CP and loadable FC

Number of connections

overall

12

usable for PG communication

11

reserved for PG communication

1

Adjustable for PG communication, min.

1

Adjustable for PG communication, max.

11

usable for OP communication

11

reserved for OP communication

1

adjustable for OP communication, min.

1

adjustable for OP communication, max.

11

usable for S7 basic communication

8

Reserved for S7 basic communication

8

adjustable for S7 basic communication, min.

0

adjustable for S7 basic communication, max.

8

S7 message functions

Number of login stations for message functions, max.

12; Depending on the configured connections for PG/OP and S7 basic communication

Process diagnostic messages

Yes

simultaneously active Alarm-S blocks, max.

40

Test commissioning functions

Status/control

Status/control variable

Yes

Variables

Inputs, outputs, memory bits, DB, times, counters

Number of variables, max.

30

of which status variables, max.

30

of which control variables, max.

14

Forcing

Forcing

Yes

Force, variables

Inputs, outputs

Number of variables, max.

10

Status block

Yes

Single step

Yes

Number of breakpoints

2

Diagnostic buffer

present

Yes

Number of entries, max.

100

adjustable

No

Configuration

Configuration software

STEP 7

Yes; V5.1 SP4 and higher

programming

Programming language

LAD

Yes

FBD

Yes

STL

Yes

SCL

Yes

CFC

Yes

GRAPH

Yes

HiGraph®

Yes

Command set

see instruction list

Nesting levels

8

Software libraries

System functions (SFC)

see instruction list

System function blocks (SFB)

see instruction list

Know-how protection

User program protection/password protection

Yes

Dimensions

Width

40 mm

  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: