6ES7313-6CE01-0AB0 SIEMENS CPU Module New

prevnext

6ES7313-6CE01-0AB0 SIEMENS CPU Module New
  • Market price: $ 3861.0
  • Shop price: $ 1170.0
  • Goods click count: 271
  • Total:
  • Quantity:
Add to cart collect
  

Description

6ES7313-6CE01-0AB0 SIEMENS CPU Module New

SIEMENS CPU Module 6ES7313-6CE01-0AB0

Product Description:

SIMATIC S7-300, CPU 313C-2DP COMPACT CPU WITH MPI, 16 DI/16 DO, 3 FAST COUNTERS (30 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 32 KBYTE WORKING MEMORY, FRONT CONNECTOR (1 X 40PIN) AND MICRO MEMORY CARD REQUIRED.

Features:

General information

Hardware product version

01

Firmware version

V2.0.0

Engineering with

Programming package

STEP 7 V5.2 SP1 or higher (with STEP 7 V5.1 SP3 or higher, please use predecessor CPU)

Supply voltage

24 V DC

Yes

permissible range, lower limit (DC)

20.4 V

permissible range, upper limit (DC)

28.8 V

Load voltage L+

Rated value (DC)

24 V

permissible range, lower limit (DC)

20.4 V

permissible range, upper limit (DC)

28.8 V

Input current

Current consumption (in no-load operation), typ.

100 mA

Inrush current, typ.

11 A

from supply voltage L+, max.

900 mA

Power losses

Power loss, typ.

10 W

Memory

Work memory

integrated

32 kbyte; For program and data

expandable

No

Load memory

pluggable (MMC)

Yes

pluggable (MMC), max.

8 Mbyte

Data management on MMC (after last programming), min.

10 a

Backup

present

Yes; Guaranteed by MMC (maintenance-free)

without battery

Yes; Program and data

CPU processing times

for bit operations, min.

0.1 µs

for bit operations, max.

0.2 µs

for word operations, min.

0.2 µs

for fixed point arithmetic, min.

2 µs

for floating point arithmetic, min.

3 µs

CPU-blocks

Number of blocks (total)

1024

DB

Number, max.

511; Number range: 1 to 511

Size, max.

16 kbyte

FB

Number, max.

512; Number range: 0 to 2047

Size, max.

16 kbyte

FC

Number, max.

512; Number range: 0 to 2047

Size, max.

16 kbyte

OB

Number, max.

see instruction list

Size, max.

16 kbyte

Number of free cycle OBs

1; OB 1

Number of time alarm OBs

1; OB 10

Number of delay alarm OBs

1; OB 20

Number of time interrupt OBs

1; OB 35

Number of process alarm OBs

1; OB 40

Number of startup OBs

1; OB 100

Number of asynchronous error OBs

1; OB 80

Number of synchronous error OBs

2; OB 121, 122

Nesting depth

per priority class

8

additional within an error OB

4

Counters, timers and their retentivity

S7 counter

Number

256

of which retentive without battery

adjustable

Yes

lower limit

0

upper limit

256

Counting range

lower limit

0

upper limit

999

IEC counter

present

Yes

Type

SFB

S7 times

Number

256

Retentivity

adjustable

Yes

lower limit

0

upper limit

256

preset

No retentivity

Time range

lower limit

10 ms

upper limit

9990 s

IEC timer

present

Yes

Type

SFB

Data areas and their retentivity

retentive data area, total

all

Flag

Number, max.

256 byte

Retentivity available

Yes; MB 0 to MB 255

Retentivity preset

MB 0 to MB 15

Number of clock memories

8

Data blocks

Number, max.

511

Size, max.

16 kbyte

Retentivity adjustable

No

Retentivity preset

Yes

Address area

I/O address area

Inputs

1 kbyte

Outputs

1 kbyte

Process image

Inputs

128 byte

Outputs

128 byte

Default addresses of the integrated channels

Digital inputs

124.0 to 125.7

Digital outputs

124.0 to 125.7

Digital channels

Inputs

8192

Outputs

8192

Inputs, of which central

992

Outputs, of which central

992

Analog channels

Inputs

248

Outputs

124

Inputs, of which central

248

Outputs, of which central

248

Hardware configuration

Racks, max.

4

Modules per rack, max.

8; In rack 3 max. 7

Expansion devices, max.

3

Number of DP masters

integrated

1

via CP

4

Number of operable FMs and CPs (recommended)

FM

8

CP, point-to-point

8

CP, LAN

6

Time of day

Clock

Hardware clock (real-time clock)

Yes

battery-backed and synchronizable

Yes

Deviation per day, max.

10 s

Backup time

6 wk

Operating hours counter

Number

1

Number/Number range

0

Range of values

0 to 2^31 hours (when using SFC 101)

Granularity

1 hour

retentive

Yes

Clock synchronization

supported

Yes

to MPI, master

Yes

to MPI, slave

Yes

in AS, master

Yes

Digital inputs

Number/binary inputs

16

integrated channels (DI)

16

Input voltage

Rated value, DC

24 V

for signal "0"

-3 to +5 V

for signal "1"

15 to 30 V

Input current

for signal "1", typ.

8 mA

Input delay (for rated value of input voltage)

for standard inputs

Parameterizable

Yes; 0.1 / 0.3 / 3 / 15 ms

for counter/technological functions

at "0" to "1", max.

8 µs

Cable length

Cable length, shielded, max.

1000 m; 100 m for technological functions

Cable length unshielded, max.

600 m

Digital outputs

Number/binary outputs

16

integrated channels (DO)

16

Functionality/short-circuit strength

Yes; Clocked electronically

Limitation of inductive shutdown voltage to

L+ (-48 V)

Output voltage

for signal "1", min.

L+ (-0.8 V)

Output current

for signal "1" permissible range for 0 to 40 °C, max.

500 mA

for signal "1" permissible range for 0 to 60 °C, max.

500 mA

for signal "1" minimum load current

5 mA

for signal "0" residual current, max.

0.5 mA

Switching frequency

with resistive load, max.

100 Hz

with inductive load, max.

0.5 Hz

Aggregate current of outputs (per group)

all mounting positions

up to 40 °C, max.

8 A

up to 60 °C, max.

4 A

Cable length

Cable length, shielded, max.

1000 m

Cable length unshielded, max.

600 m

Encoder

Connectable encoders

2-wire BEROS

Yes

permissible quiescent current (2-wire BEROS), max.

1.5 mA

Interfaces

MPI

Cable length, max.

50 m; without repeater

1st interface

Type of interface

Integrated RS 485 interface

Physics

RS 485

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

200 mA

Functionality

MPI

Yes

DP master

No

DP slave

No

Point-to-point connection

No

MPI

Number of connections

8

Services

PG/OP communication

Yes

Routing

Yes

Global data communication

Yes

S7 basic communication

Yes

S7 communication

Yes

S7 communication, as client

No

S7 communication, as server

Yes

Transmission rate, max.

187.5 kbit/s

2nd interface

Type of interface

Integrated RS 485 interface

Physics

RS 485

Isolated

Yes

Power supply to interface (15 to 30 V DC), max.

200 mA

Media redundancy

Number of connection resources

8

Functionality

MPI

No

DP master

Yes

DP slave

Yes

Local Operating Network

No

DP master

Number of connections, max.

8; For PG/OP communication

Services

PG/OP communication

Yes

Routing

Yes

Global data communication

No

S7 basic communication

Yes

S7 communication

Yes

S7 communication, as client

No

S7 communication, as server

Yes

Equidistance mode support

Yes

SYNC/FREEZE

Yes

Activation/deactivation of DP slaves

Yes

Direct data exchange (slave-to-slave communication)

Yes

DPV1

Yes

Transmission rate, max.

12 Mbit/s

  

User Comment

No comment
Username: Anonymous user
E-mail:
Rank:
Verification code: captcha
Content: