No comment |
>
Control System >
PLC >
Siemens PLC >
6ES7313-6CE01-0AB0 SIEMENS CPU Module New6ES7313-6CE01-0AB0 SIEMENS CPU Module NewSIEMENS CPU Module 6ES7313-6CE01-0AB0
Product Description:
SIMATIC S7-300, CPU 313C-2DP COMPACT CPU WITH MPI, 16 DI/16 DO, 3 FAST COUNTERS (30 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 32 KBYTE WORKING MEMORY, FRONT CONNECTOR (1 X 40PIN) AND MICRO MEMORY CARD REQUIRED.
Features:
General information
Hardware product version
01
Firmware version
V2.0.0
Engineering with
Programming package
STEP 7 V5.2 SP1 or higher (with STEP 7 V5.1 SP3 or higher, please use predecessor CPU)
Supply voltage
24 V DC
Yes
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Load voltage L+
Rated value (DC)
24 V
permissible range, lower limit (DC)
20.4 V
permissible range, upper limit (DC)
28.8 V
Input current
Current consumption (in no-load operation), typ.
100 mA
Inrush current, typ.
11 A
from supply voltage L+, max.
900 mA
Power losses
Power loss, typ.
10 W
Memory
Work memory
integrated
32 kbyte; For program and data
expandable
No
Load memory
pluggable (MMC)
Yes
pluggable (MMC), max.
8 Mbyte
Data management on MMC (after last programming), min.
10 a
Backup
present
Yes; Guaranteed by MMC (maintenance-free)
without battery
Yes; Program and data
CPU processing times
for bit operations, min.
0.1 µs
for bit operations, max.
0.2 µs
for word operations, min.
0.2 µs
for fixed point arithmetic, min.
2 µs
for floating point arithmetic, min.
3 µs
CPU-blocks
Number of blocks (total)
1024
DB
Number, max.
511; Number range: 1 to 511
Size, max.
16 kbyte
FB
Number, max.
512; Number range: 0 to 2047
Size, max.
16 kbyte
FC
Number, max.
512; Number range: 0 to 2047
Size, max.
16 kbyte
OB
Number, max.
see instruction list
Size, max.
16 kbyte
Number of free cycle OBs
1; OB 1
Number of time alarm OBs
1; OB 10
Number of delay alarm OBs
1; OB 20
Number of time interrupt OBs
1; OB 35
Number of process alarm OBs
1; OB 40
Number of startup OBs
1; OB 100
Number of asynchronous error OBs
1; OB 80
Number of synchronous error OBs
2; OB 121, 122
Nesting depth
per priority class
8
additional within an error OB
4
Counters, timers and their retentivity
S7 counter
Number
256
of which retentive without battery
adjustable
Yes
lower limit
0
upper limit
256
Counting range
lower limit
0
upper limit
999
IEC counter
present
Yes
Type
SFB
S7 times
Number
256
Retentivity
adjustable
Yes
lower limit
0
upper limit
256
preset
No retentivity
Time range
lower limit
10 ms
upper limit
9990 s
IEC timer
present
Yes
Type
SFB
Data areas and their retentivity
retentive data area, total
all
Flag
Number, max.
256 byte
Retentivity available
Yes; MB 0 to MB 255
Retentivity preset
MB 0 to MB 15
Number of clock memories
8
Data blocks
Number, max.
511
Size, max.
16 kbyte
Retentivity adjustable
No
Retentivity preset
Yes
Address area
I/O address area
Inputs
1 kbyte
Outputs
1 kbyte
Process image
Inputs
128 byte
Outputs
128 byte
Default addresses of the integrated channels
Digital inputs
124.0 to 125.7
Digital outputs
124.0 to 125.7
Digital channels
Inputs
8192
Outputs
8192
Inputs, of which central
992
Outputs, of which central
992
Analog channels
Inputs
248
Outputs
124
Inputs, of which central
248
Outputs, of which central
248
Hardware configuration
Racks, max.
4
Modules per rack, max.
8; In rack 3 max. 7
Expansion devices, max.
3
Number of DP masters
integrated
1
via CP
4
Number of operable FMs and CPs (recommended)
FM
8
CP, point-to-point
8
CP, LAN
6
Time of day
Clock
Hardware clock (real-time clock)
Yes
battery-backed and synchronizable
Yes
Deviation per day, max.
10 s
Backup time
6 wk
Operating hours counter
Number
1
Number/Number range
0
Range of values
0 to 2^31 hours (when using SFC 101)
Granularity
1 hour
retentive
Yes
Clock synchronization
supported
Yes
to MPI, master
Yes
to MPI, slave
Yes
in AS, master
Yes
Digital inputs
Number/binary inputs
16
integrated channels (DI)
16
Input voltage
Rated value, DC
24 V
for signal "0"
-3 to +5 V
for signal "1"
15 to 30 V
Input current
for signal "1", typ.
8 mA
Input delay (for rated value of input voltage)
for standard inputs
Parameterizable
Yes; 0.1 / 0.3 / 3 / 15 ms
for counter/technological functions
at "0" to "1", max.
8 µs
Cable length
Cable length, shielded, max.
1000 m; 100 m for technological functions
Cable length unshielded, max.
600 m
Digital outputs
Number/binary outputs
16
integrated channels (DO)
16
Functionality/short-circuit strength
Yes; Clocked electronically
Limitation of inductive shutdown voltage to
L+ (-48 V)
Output voltage
for signal "1", min.
L+ (-0.8 V)
Output current
for signal "1" permissible range for 0 to 40 °C, max.
500 mA
for signal "1" permissible range for 0 to 60 °C, max.
500 mA
for signal "1" minimum load current
5 mA
for signal "0" residual current, max.
0.5 mA
Switching frequency
with resistive load, max.
100 Hz
with inductive load, max.
0.5 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 40 °C, max.
8 A
up to 60 °C, max.
4 A
Cable length
Cable length, shielded, max.
1000 m
Cable length unshielded, max.
600 m
Encoder
Connectable encoders
2-wire BEROS
Yes
permissible quiescent current (2-wire BEROS), max.
1.5 mA
Interfaces
MPI
Cable length, max.
50 m; without repeater
1st interface
Type of interface
Integrated RS 485 interface
Physics
RS 485
Isolated
Yes
Power supply to interface (15 to 30 V DC), max.
200 mA
Functionality
MPI
Yes
DP master
No
DP slave
No
Point-to-point connection
No
MPI
Number of connections
8
Services
PG/OP communication
Yes
Routing
Yes
Global data communication
Yes
S7 basic communication
Yes
S7 communication
Yes
S7 communication, as client
No
S7 communication, as server
Yes
Transmission rate, max.
187.5 kbit/s
2nd interface
Type of interface
Integrated RS 485 interface
Physics
RS 485
Isolated
Yes
Power supply to interface (15 to 30 V DC), max.
200 mA
Media redundancy
Number of connection resources
8
Functionality
MPI
No
DP master
Yes
DP slave
Yes
Local Operating Network
No
DP master
Number of connections, max.
8; For PG/OP communication
Services
PG/OP communication
Yes
Routing
Yes
Global data communication
No
S7 basic communication
Yes
S7 communication
Yes
S7 communication, as client
No
S7 communication, as server
Yes
Equidistance mode support
Yes
SYNC/FREEZE
Yes
Activation/deactivation of DP slaves
Yes
Direct data exchange (slave-to-slave communication)
Yes
DPV1
Yes
Transmission rate, max.
12 Mbit/s
No comment |