Description

6ES7135-0HF01-0XB0 SIEMENS ELECTRONIC MODULE FOR ET 200B New

SIEMENS ELECTRONIC MODULE FOR ET 200B 6ES7135-0HF01-0XB0

Product Description:

SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S.

Features:

Supply voltage

Rated value (DC)

24 V; Value at t < 0.5 s: 35 V

permissible range, lower limit (DC)

18.5 V

permissible range, upper limit (DC)

30.2 V

Input current

from supply voltage L+, max.

200 mA; Logic

Power losses

Power loss, typ.

2.4 W

Hardware configuration

Rack

Required terminal block

TB8

Digital outputs

Load resistance range

Load impedance in rated range of output , capacitive load, max.

1 µF

Analog outputs

Number of analog outputs

4

Voltage output, short-circuit protection

Yes; Electronic; max. 1 output in parallel

Voltage output, short-circuit current, max.

25 mA

Current output, no-load voltage, max.

18 V

Output ranges, voltage

0 to 10 V

Yes

-10 to +10 V

Yes

Output ranges, current

0 to 20 mA

Yes

4 to 20 mA

Yes

Connection of actuators

for voltage output 2-conductor connection

Yes

for voltage output 4-conductor connection

Yes

for current output 2-conductor connection

Yes

Load impedance (in rated range of output)

with current outputs, max.

300 Ω

with current outputs, inductive load, max.

1 mH

Cable length

Cable length, shielded, max.

100 m

Analog value creation

Integrations and conversion time/ resolution per channel

Resolution with overrange (bit including sign), max.

11 bit; Two's complement

Conversion time (per channel)

1 ms

Settling time

for resistive load

0.1 ms

for capacitive load

3.3 ms

for inductive load

0.5 ms

Errors/accuracies

Output ripple (based on output area, bandwidth 0 to 50 kHz)

+/- 0.05 %

Linearity error (relative to output area)

+/- 0.05 %

Temperature error (relative to output area)

+/- 0.02 %

Crosstalk between the outputs, min.

40 dB

Repeat accuracy in settled status at 25 °C (relative to output area)

+/- 0.05 %

Operational limit in overall temperature range

Voltage, relative to output area

+/- 0.05 %

Current, relative to output area

+/- 1 %

Basic error limit (operational limit at 25 °C)

Voltage, relative to output area

+/- 0.2 %

Current, relative to output area

+/- 0.3 %

Interfaces

PROFIBUS DP

Transmission rate, max.

12 Mbit/s

Communication functions

Bus protocol/transmission protocol

PROFIBUS DP

Interrupts/diagnostics/status information

Alarms

Diagnostic alarm

Yes; Parameterizable

Diagnostics indication LED

Bus fault BF (red)

Yes

Run mode RUN (green)

Yes

Galvanic isolation

between electronic block and PROFIBUS DP

Yes

Galvanic isolation analog outputs

Galvanic isolation analog outputs

No

Ambient conditions

Operating temperature

horizontal installation, min.

0 °C

horizontal installation, max.

60 °C; 40°C for other mountings

Air pressure

permissible range, min.

795 hPa

permissible range, max.

1080 hPa

Relative humidity

Operation, min.

15 %

Operation, max.

95 %; RH class 2 in accordance with IEC 1131-2

Vibrations

Operation, checked according to IEC 60068-2-6

Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)

Shock test

checked according to IEC 60068-2-27

Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms

Degree and class of protection

IP20

Yes

Connection method

Inputs/outputs

Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection

Dimensions

Width

160 mm; EB and TB

Height

130 mm; EB and TB

Depth

60 mm; EB and TB

Weight

Weight, approx.

550 g; EB and TB



  