6ES7131-1BL01-0XB0 SIEMENS ELECTRONIC MODULE New

SIEMENS ELECTRONIC MODULE 6ES7131-1BL01-0XB0

Product Description:

SIMATIC DP, ELECTRONIC BLOCK FOR ET 200L, 32 DI, 24V DC.

Features:

Supply voltage

24 V DC

Yes

Reverse polarity protection

Yes

Hardware configuration

Rack

Required terminal block

TB 32L

Digital inputs

Number/binary inputs

32

Input voltage

Type of input voltage

DC

Rated value, DC

24 V

for signal "0"

-30 to +5 V

for signal "1"

13 to 30 V

Input current

for signal "1", typ.

5 mA

Input delay (for rated value of input voltage)

for standard inputs

at "0" to "1", min.

2 ms

at "0" to "1", max.

4.5 ms

Cable length

Cable length for NAMUR input, shielded, max.

1000 m

Interfaces

PROFIBUS DP

Transmission rate, max.

1.5 Mbit/s

Direct data exchange (slave-to-slave communication)

Yes; Transmitter (for digital outputs and hybrid modules ET 200L: not for L-SC or IM-SC)

Galvanic isolation

between PROFIBUS DP and all other circuit components

Yes

Galvanic isolation digital inputs

between the channels

No

between the channels and PROFIBUS DP

Yes

Degree and class of protection

IP20

Yes

Ambient conditions

Operating temperature

horizontal installation, min.

0 °C

horizontal installation, max.

60 °C; 40°C for other mountings

Air pressure

permissible range, min.

795 hPa

permissible range, max.

1080 hPa

Relative humidity

Operation, min.

5 %

Operation, max.

95 %; RH class 2 in accordance with IEC 1131-2

Vibrations

Operation, checked according to IEC 60068-2-6

Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)

Shock test

checked according to IEC 60068-2-27

Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms

Connection method

Inputs/outputs

Screw-type and spring-loaded terminals, permanent wiring; standard: 2-wire connection, optional: 3 and 4-wire connection

Dimensions

Width

145 mm

Height

60 mm

Depth

60.5 mm

 



  